![ABB IEC 61850 Edition 2 Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/abb/iec-61850-edition-2/iec-61850-edition-2_communication-protocol-manual_2732050.webp)
A GOOSE message is forced to be transmitted when a trigger change is detected
for a data attribute. All members of the data set are copied in the send buffer with
their actual value and the message is sent. The subscribers, who knows the address
of this GOOSE message, receives the telegram. The GOOSE message includes a
sequence number to verify that all messages are received.
Section 6
1MRK 511 393-UEN A
Data sets and control blocks
44
670 series 2.2 IEC
Communication protocol manual