![ABB IEC 61850 Edition 2 Скачать руководство пользователя страница 48](http://html.mh-extra.com/html/abb/iec-61850-edition-2/iec-61850-edition-2_communication-protocol-manual_2732048.webp)
6.3
GOOSE Control Blocks (GoCB)
SEMOD129786-83 v7
en06000109.vsd
S
e
nd
Data-set
R
e
ce
iv
e
R
e
ce
iv
e
LN
LN
LN
LN
LN
S
e
nd
Data-set
R
e
ce
iv
e
R
e
ce
iv
e
LN
LN
LN
LN
S
e
nd
Data-set
R
e
ce
iv
e
R
e
ce
iv
e
LN
LN
LN
LN
LN
LN
Subnetwork
LN0
GoCB
DataSet
Input
GoCB
GoCB
DataSet
DataSet
Input
Input
Comm.
GSE
LD0
Server
LN0
GoCB
DataSet
Input
GoCB
GoCB
DataSet
DataSet
Input
Input
Comm.
GSE
LD0
Server
IEC06000109 V2 EN-US
Figure 10:
IEC 61850: Principle operation of GOOSE messages
The Generic Object Oriented Substation Event (GOOSE) class model is used to
distribute input and output data values between IEDs on bay level (in horizontal
direction) through the use of multicast services. GOOSE messages enable fast
transmission from a publisher to one or several subscribers (receivers).
The GOOSE service model of IEC 61850-7-2 provides the possibility for fast and
reliable system-wide distribution of input and output data values. This
implementation uses a specific scheme of re-transmission to achieve the
appropriate level of reliability. When a GOOSE server generates a
SendGOOSEMessage request, the current data set values are encoded in a GOOSE
message and transmitted on the multicast association. The event that causes the
Section 6
1MRK 511 393-UEN A
Data sets and control blocks
42
670 series 2.2 IEC
Communication protocol manual