
ABB i-bus® KNX
PARAMETERS
7.4.13
Type of control value Basic-stage heating
This parameter is used to specify the control and control value type for the basic-stage heating.
Note
The parameter can be changed only if, in the parameter
Basic-stage heating [controller]
, the option
Free configuration
is selected.
Note
For a detailed description: →
.
Option
2-point 1 bit (On/Off)
The following dependent group objects are displayed:
•
Status Control value basic-stage heating
(DPT 1.001)
2-point 1 byte (0/100 %)
The following dependent group objects are displayed:
•
Status Control value basic-stage heating
(DPT 5.001)
PI continuous (0 … 100 %)
The following dependent parameters are shown:
•
•
The following dependent group objects are displayed:
•
Status Control value basic-stage heating
(DPT 5.001)
PI PWM (On/Off)
The following dependent parameters are shown:
•
•
The following dependent group objects are displayed:
•
Status Control value basic-stage heating
(DPT 1.001)
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
• The parameter is in the parameter window
parameter window
.
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
62
Note about navigation in the PDF: Key combination 'Alt + left arrow'
jumps to the previous view/page