ABB i-bus® KNX
GROUP OBJECTS
8.6
Group objects Channel X – Controller
Function
Group object name
Data point
type
Length
Flags
Status Heating/cooling
Channel X – Controller
DPT 1.100
1 bit
C R
T
This group object sends the status
Heating
/
cooling
on the bus (ABB i-bus® KNX).
Telegram value:
•
1 = Heating
•
0 = Cooling
Note
If the channel is operated as a controller (master) and controls an actuator (slave), the actuator (slave) is switched between
Heating
and
Cooling
is this group
object.
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage heating [controller]
all options except
Deactivated
–
Basic-stage cooling [controller]
\
all options except
Deactivated
–
Type of heating/cooling system
Option
4-pipe
–
Options
Automatic / Via group object or via slave
Status Control value basic-
stage heating
Channel X – Controller
DPT 5.001
1 byte
C R
T
This group object sends the control value for basic-stage heating on the bus (ABB i-bus® KNX).
The data point type depends on the option selected in the parameter
Basic-stage heating [controller]
and the associated control type. A control type is preset
depending on the option. Any control type can be selected if the option
Free configuration
is selected.
Output is via a 1-byte value (DPT 5.001) with the following control types:
•
2-point 1 byte (0/100 %)
•
PI continuous (0 … 100 %)
•
PI continuous (0 … 100 %) for fan coil
Telegram value:
•
0 … 100 %
Note
If DPT 5.001 (percentage) is used for the activation, the value displayed for the group object may vary from the actual value due to rounding differences. The actual
value of the group object can be seen by viewing the hexadecimal value (e.g. 0x0001) or by changing to a different DPT (e.g. DPT 5.005) in the ETS.
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage heating [controller]
Options
Convector (e.g. radiator)/ Area heating (e.g. floor) / Free configuration
Status Control value basic-
stage heating
Channel X – Controller
DPT 1.001
1 bit
C R
T
This group object sends the control value for basic-stage heating on the bus (ABB i-bus® KNX).
The data point type depends on the option selected in the parameter
Basic-stage heating [controller]
and the associated control type. A control type is preset
depending on the option. Any control type can be selected if the option
Free configuration
is selected.
Output is via a 1-bit value (DPT 1.001) for the following control types:
•
2-point 1 bit (On/Off)
•
PI PWM (On/Off)
Telegram value:
•
1 = On
•
0 = Off
Prerequisites for visibility
•
Application parameters, Page 36
–
Option
Controller channel
–
Basic-stage heating [controller]
Option
Free configuration
Status Control value additional-
stage heating
Channel X – Controller
DPT 5.001
1 byte
C R
T
This group object sends the control value for additional-stage heating on the bus (ABB i-bus® KNX).
The data point type depends on the option selected in the parameter
and the associated control type. A control type is preset depending on
the option. Any control type can be selected if the option
Free configuration
is selected.
Output is via a 1-byte value (DPT 5.001) with the following control types:
•
2-point 1 byte (0/100 %)
•
PI continuous (0 … 100 %)
•
PI continuous (0 … 100 %) for fan coil
Telegram value:
•
0 … 100 %
Note
If DPT 5.001 (percentage) is used for the activation, the value displayed for the group object may vary from the actual value due to rounding differences. The actual
value of the group object can be seen by viewing the hexadecimal value (e.g. 0x0001) or by changing to a different DPT (e.g. DPT 5.005) in the ETS.
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage heating [controller]
all options except
Deactivated
–
Options
Convector (e.g. radiator) / Area heating (e.g. floor) / Free configuration
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B