background image

DGN/S 1.16.1

DGN/S 1.16.1

ABB i-bus

®

 KNX

DALI Gateway, Emergency Lighting, MDRC
DGN/S 1.16.1, 2CDG 110 142 R0011

2CDC 071 009 S0011

Page 1 of 4

DGNS_1161_TD_EN_V1-0

2CDC 507 115 D0201

8

8

The KNX ABB i-bus

®

 DALI Gateway 

with Emergency Lighting Function 
DGN/S 1.16.1 is a KNX modular 
installation device (MDRC) in Pro 

M

-

design for installation in the distribution 
board on 35 mm mounting rails. 

The DGN/S integrates operating de-
vices with DALI interfaces to EN 62386 
into a KNX building installation. 
The connection to the ABB i-bus

®

 is 

implemented via a KNX connection 
terminal on the device shoulders.

The DALI output of the DGN/S can be 
used to connect up to 64 DALI devices. 
It can also exclusively contain 64 DALI 
devices for self-contained emergency 
lighting compliant to EN 6286-202. 
Both “normal” lamps as well as battery 
operated emergency lighting can be 
connected in a mixed configuration to 
the DGN/S 1.16.1.

Control of the lamps via KNX is under-
taken by 16 lighting groups, which can 
be comprised of any 64 DALI lamps. 

An individual project-related DALI 
device group assignment is possible 
using the DALI-Software-Tool. 

 

The fault status (lamps, ballasts or 
emergency light converter) of every 
individual DALI device or of the 
lighting group is sent via different KNX 
communication objects on the KNX.

In addition to the standard functions, 
e.g. switching, dimming and brightness 
value setting with the corresponding 
feedbacks, the DGN/S has the 
functions Staircase lighting, Scene, 
Sequence and Slave. The lighting 
groups can be integrated in this way 
into a constant lighting control. 

Function, duration and partial duration 
tests and battery tests for the emer-
gency lighting systems with individual 
batteries to EN 62386-202 can be trig-
gered and stopped via KNX. The test 
results are made available on the KNX.

All DALI devices can be controlled 
together in KNX mode as well as 
manual mode.

The DGN/S is a DALI control device 
(master) and requires an AC or DC 
auxiliary power supply. A separate 
DALI power supply is not required. 
The DALI power source for the 64 DALI 
devices is integrated into the DGN/S. 

Technical data

Supply

gateway operating voltage

power consumption total via mains

current consumption total via mains

leakage loss total for device

current consumption KNX

power consumption via KNX

85…265 V AC, 50/60 Hz
110…240 V DC

maximum 8 W at 230 V AC and max. load

maximum 35 mA at 230 V AC and max. load

maximum 3 W at 230 V AC and max. load

maximum 10 mA

maximum 210 mW

DALI outputs (channels)

number of outputs

number of DALI devices

distance between DGN/S and last DALI device 
cable cross-section   0.5 mm

2

 

   

0.75 

mm

2

   

1.0 

mm

2

   

1.5 

mm

2

1 x 64 DALI device (16 lighting groups)

maximum 64 to EN 62 386; DALI devices 
pfor self-contained emergency lighting to 
EN 62 386-202 are supported.

2)

100 m

1) 

150 m

1)

 

200 m

1)

300 m

1)

Connections

KNX

DALI outputs and mains voltage

tightening torque

KNX connection terminal, 0.8 mm Ø, 
single core

screw terminal 
0.2…2.5 mm

2

 stranded 

0.2…4 mm

2

    single core

maximum 0.6 Nm

Содержание i-bus DGN/S 1.16.1

Страница 1: ...he corresponding feedbacks the DGN S has the functions Staircase lighting Scene Sequence and Slave The lighting groups can be integrated in this way into a constant lighting control Function duration and partial duration tests and battery tests for the emer gency lighting systems with individual batteries to EN 62386 202 can be trig gered and stopped via KNX The test results are made available on ...

Страница 2: ...C 160 mA 230 mA Temperature range operation storage transport 5 C 45 C 25 C 55 C 25 C 70 C Environmental conditions humidity maximum 93 moisture condensation should be excluded Design modular installation device MDRC dimensions mounting width mounting depth modular installation device Pro M 90 x 72 x 64 5 mm H x W x D 4 modules at 18 mm 68 mm Installation on 35 mm mounting rail to EN 60 715 Mounti...

Страница 3: ...ilable free of charge at www abb com knx The ETS and the current version of the device application program are required for programming The current version of the application program is available for download on the internet at www abb com knx After import in the ETS it is available in the ETS under ABB Lighting DALI Switch Dim Emergency 1f DALI The device does not support the closing function of ...

Страница 4: ...N_V1 0 2CDC 507 115 D0201 8 8 Circuit diagram Dimension drawing 2CDC 072 014 F0011 1 Label carrier 2 Button KNX 3 LED KNX 4 Connection terminal KNX 5 LED DALI fault 6 LED Gateway ON 7 Gateway operating voltage 8 Output DALI 9 Button DALI 10 DALI device without with function emergency lighting with individual battery 2CDC 072 012 F0011 ...