ABB HVL 120-0.3 Скачать руководство пользователя страница 10

 

Operating manual HVL 120-0.3 

 

 

Before beginning the work, check the safety distance to adjacent live parts or 
equipment. If there is a danger of inadvertent touching, the 5 safety rules for 
establishing and securing the de-energised condition at the work location must be 
carried out (see the section entitled Safety instructions). 

 

 

 

 
Secure yourself against falling if the intended mounting position is on a mast or on a 
high-level structure. For this purpose, use a secure working platform and wear your 
personal protective equipment.

 

 
A low voltage limiter must not be removed from the electrical circuit until its operating condition has been 
determined! For this, proceed as follows: 
 

1.  Measure the voltage via the connections of the HVL 120-0.3 with a measuring device suitable for DC 

voltage. 

2.  Measure the current through the HVL 120-0.3 with a current probe suitable for DC current. 

During 

this operation, never disconnect a connection! Otherwise, there is the danger of an electric 
shock.

 

3.  If the voltage measurement gives a value greater than 50 V or the current measurement gives a 

value greater than 0.3 A, then first of all the cause must be determined. If the cause is found and 
rectified, the checks under Point 1. and Point 2. must be repeated. 

4.  The HVL 120-0.3 must be shorted out with a conductor of sufficient dimensions (observe the 

national regulations and the requirements of the railway network operator). This conductor must be 
arranged to ensure that detachment of the connection during removal of the HVL 120-0.3 cannot 
occur. 

5.  Take a further measurement of the voltage via the connections of the HVL 120-0.3 with a measuring 

device suitable for DC voltage. The voltage measurement should now give a value less than 1 V. If 
this is the case, then the HVL 120-0.3 can be removed. Otherwise, the current circuit must be 
checked again. 

6.  The volume resistance of the HVL 120-0.3 can now be measured with a standard Multimeter 

3)

. The 

resistance value obtained must be at least 1 k

. If this is not the case, then the HVL 120-0.3 is 

defective and must be replaced. If the resistance value is equal to, or greater than 1 k

, it can be 

concluded that the thyristors are functional, and the HVL 120-0.3 can be re-fitted. 

7.  The conductor used for shorting-out, must only be removed when the HVL 120-0.3 has been 

completely re-fitted. 

 

3)

 For the resistance measurement, do not use an insulation resistance meter (Megger)! This could lead to a 

false evaluation, since such measuring devices work at voltage levels which will cause the low voltage limiter 
to change into its conductive state.  

1HC0023892 AA 

EN 

Page 10 / 12

 

Содержание HVL 120-0.3

Страница 1: ...L DATA DESIGN 4 5 OPERATION AND STRUCTURE 6 6 ASSEMBLY AND INSTALLATION 7 7 MAINTENANCE SERVICING 9 8 SQS CERTIFICATE 11 9 EU DECLARATION OF CONFORMITY 11 Published by Contact details ABB Switzerland Ltd Phone 41 58 585 29 11 Surge arresters Telefax 41 58 585 55 70 Jurastrasse 45 E mail sales sa ch abb com CH 5430 Wettingen 1 www abb com arrestersonline Switzerland Subject to change without notice...

Страница 2: ...of installation ABB accepts no liability for direct or indirect damage arising from the use or misuse of this product 2 DESCRIPTION AND FUNCTION Stationary installations for the supply of railway traction current employ the rails amongst other means as the return path for the traction current In the case of DC current railways electrically conductive parts or structures located in the area of the ...

Страница 3: ...miter Each consignment is accompanied by final inspection record Scope of supply Low voltage limiter Fixing bracket for the low voltage limiter T bracket for cable connection Bolts and tension washers Final inspection record 1 x 1 x 1 x 4 x 1 x Following delivery each consignment must be checked for completeness and correctness compare against the order and delivery documents In the case of incomp...

Страница 4: ...s current value in the stated time period the low voltage limiter resets itself back to its starting condition after responding If the current is higher than this or if the time period is greater than that stated the resetting capability cannot be guaranteed If the low voltage limiter does not reset to its starting condition it becomes permanently conductive In this way the protective function con...

Страница 5: ...l HVL 120 0 3 Up Residual voltage at nominal discharge current In No HA Serial number Dimensions Low voltage limiter T bracket for cable connection Fixing bracket for the low voltage limiter 1HC0023892 AA EN Page 5 12 ...

Страница 6: ... voltage U applied to the low voltage limiter and typically lies in the region of several hundred microseconds The duration of the overvoltage is therefore the controlling factor for the value of the voltage limitation If the duration lies in the region of several hundred microseconds then the characteristic curve of the metal oxide varistor alone defines the voltage limitation for example 380 V a...

Страница 7: ...r must only be assembled installed and operated with the supplied accessories for its intended purpose and in accordance with its specifications o Modifications and repairs to the low voltage limiter itself and to its mounting parts are prohibited o If special problems arise which were not covered or were insufficiently covered in this operating manual please contact ABB Schweiz Before beginning a...

Страница 8: ...ure For this purpose use a secure working platform and wear your personal protective equipment The contact surface to which the low voltage limiter is to be fitted by means of the fixing bracket must be flat and clean The mounting position of the low voltage limiter can be freely chosen It must be noted however that the type plate and serial number should remain easily readable without removing th...

Страница 9: ...ltage limiter should be cleaned For this we recommend that a soft cloth is used with warm water and a mild household cleaner do not use solvents or abrasive cleaning agents Faults and reserve equipment The low voltage limiter is a protective equipment element and therefore overloading can never be completely excluded Depending on the number of units in operation it is recommended that a suitable n...

Страница 10: ...under Point 1 and Point 2 must be repeated 4 The HVL 120 0 3 must be shorted out with a conductor of sufficient dimensions observe the national regulations and the requirements of the railway network operator This conductor must be arranged to ensure that detachment of the connection during removal of the HVL 120 0 3 cannot occur 5 Take a further measurement of the voltage via the connections of t...

Страница 11: ...red and brought into service in conformity with the EC directive 73 23 EEC Company ABB Switzerland Ltd Surge arresters Jurastrasse 45 CH 5430 Wettingen Switzerland The following EC directives and harmonised standards have been applied EC directive 73 23 EEC low voltage electrical equipment The following European standards have been applied Railway applications stationary installations DC current s...

Страница 12: ...Operating manual HVL 120 0 3 1HC0023892 AA EN Page 12 12 ...

Отзывы: