1.4.1 Fault finding chart
FAULT
CAUSE
REMEDY
Spring will not charge
Motor has wrong or no
Measure voltage on the
operating voltage
motor leads.
Motor shaft broken
Change motor
Motor gear damage
Change motor
The latch for tripping
Check mechanism
device does not function
NOTE: Read safety
instruction in paragraph
1.3 before taking action
Disconnection in the wires Check by measuring.
Closing of breaker does not
Operating coil does not pull Measure the voltage,
take place although there
adjust the coils adjust-
is an indication that the
ment screw.
springs are tensioned.
Check breaker springs
Breaker closes then opens
The toggle joint of the
Adjust the toggle joint
again.
mechanism are incorrectly
adjusted
Main circuit is wrong
Find fault and adjust
Wrongly adjusted
clearance of opening
Adjust
magnets armature
Breaker continuously opens
Anti-pumping relay wrong Change relay
and closes
Breaker will not close
Micro-switch arm wrongly
Find fault and adjust
completely
adjusted
Under-voltage relay
Find fault and adjust
released.
(18)