Additional explanation
No. 1: The input terminal for the control supply voltage is 24 V DC. Its reference potential is the terminal right next to it,
labeled with '
⊥
'.
No. 2: For DOLE-types there is one control input, which starts the motor. For ROLE-types, the 'R' terminal is for forward
running (right rotation); 'L' is for reverse running (left rotation) of the motor.
No. 3: Regardless of whether it is a DOLE or a ROLE device, there is one reference potential terminal for the control input
(ON/ R, L).
No. 4: After the overload function has tripped, the compact starter can be reset automatically, manually and remotely using
these terminals. For manual reset, press the reset button. Remote reset requires the connection of a button (N/O contact)
between MAN an RES terminals. Establish an electrical connection between the RES and AUT terminals for automatic reset.
No. 5: The feedback relay is activated as soon as the electronic compact starter detects an error or indicates a message: the
N/O contact between terminals 96 and 97 is closed or the N/C contact between terminals 95 and 96 is opened.
No. 12: The output voltage terminal has to be connected with the motor.
No. 14: The input voltage terminal has to be connected with the 3-phase supply network. Please also establish device and
wire protection.