6 Go pulse dn
Edit the go pulse down.
7 Offset
up
Edit the up offset.
8 Offset
down
Edit the down offset.
9 ADC
noise
Edit the noise band.
2 Auto
configuration
1 Auto
conf
modes
With this menu item you can select the desired auto-configuration mode. Options:
- Complete auto-configuration
- Control parameters only
- Valve range only
- Zero only
2 Auto
conf
locked
With this option you can disable auto-configuration. Press
to activate (ON) or
deactivate (OFF) the lock.
3 Start
auto
conf
Press
to select this option. The message "Initialized" appears in the display,
unless auto-configuration has been locked. Press
(OK) to confirm and start
the auto-configuration function. The message "Auto configuration is running" is
seen in the display. After successful completion the message "Auto configuration
done" appears. You can either press
(OK) to save the data in the TZID-C/
TZID-C200’s non-volatile memory, or press
(ABORT) to reject the data. Note
that a running auto-configuration can be stopped at any time by pressing
(ABORT).
3 Options
1 Analg
pos
feedback
1 Output
min
Enter the current for 0 % stroke (travel). The current is entered as a percentage of
the 4...20 mA range (= 16 mA) , plus 4 mA offset.
Example:
100% = 20 mA (16 mA range + 4 mA offset)
0% = 4 mA (0 mA range + 4 mA offset)
10% = 5.6 mA (1.6 mA range + 4 mA offset)
2 Output
max
Enter the current for 100% stroke (travel). The current is entered as a percentage
(see item 1).
3 Output
action
Select the output action for the module for "analog position feedback".
4 Alarm
messages
Select the alarm current for alarm reporting of the module for "analog position
feedback". Options: "> 20 mA" or "< 4 mA"