Installation and maintenance guide
1ZSC000563-AAX EN, REV. A, 2019-03-21
29
4.5 Installation with draw rod at site
G004175
1
Upper draw rod
2
Flexible pull-through cord
3
Lower draw rod with bottom contact
4
Bottom contact
5
Bushing
Procedure
NOTE!
This procedure is only valid if the lower draw rod with bottom contact (5) is already installed in
the transformer.
1.
Apply Vaseline to the thread on the pull-through
cord (12), and then connect it to the draw rod.
NOTE!
Or use a lubricant with equal properties
to Vaseline.
G003144