Installation and maintenance guide
1ZSC000563-AAX EN, REV. A, 2019-03-21
39
4.8 Flashover distance
The distance to external objects from the top of the bushing is very important for the safe operation of
the bushing.
A clear area around the high voltage end of the bushing must be maintained, to prevent flashover or other
disturbances. The radius of the area corresponds to the arcing distance of the bushing insulator.
CAUTION!
Objects in the flashover distance can cause a spontaneous electrical discharge.
G004180
1
Flashover distance
Type
Flashover distance (mm)
GSC 200
2045
GSC 300
3540
GSC 300E
2855
GSC 400
4230
GSC 450S
3760
GSC 450E
5100
GSC 500
5100
GSC 500E
5100