![ABB GSB 245 Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/abb/gsb-245/gsb-245_technical-manual_4051006.webp)
6
TR A N S FOR M E R BUS H I NG S T Y PE G S B
T EC H N I C A L G U I D E
—
Table 1. General specifications
For conditions exceeding the standard specification, please consult the supplier.
Application:
Transformers
Classification:
Resin impregnated paper, capacitance graded, outdoor immersed bushing,
temperature class E (120 °C) according to IEC 60137
Ambient temperature:
+40 to -40 °C (-60 °C according to GOST 10693-81 in applicable parts.)
Altitude of site:
< 1000 m
Level of rain and humidity:
1-2 mm rain/min. horizontally and vertically, as per IEC 60060-1, and 5 mm/min. as per
IEEE
Pollution level:
According to specific creepage distance and IEC 60815
Immersion medium:
Transformer oil.
Oil temperatures for normal load:
Maximum daily mean tempe90 °C. Maximum temporary temperature: +100 °C.
Oil temperatures for long and short time overload:
Maximum daily mean tempe90 °C. Maximum temporary temperature: +115 °C.
Max pressure of medium:
100 kPa (over pressure)
Angle of mounting:
Horizontal to vertical
Test tap:
Dimensions according to IEEE Potential tap type A. U
r
= max. 600 V
Voltage tap:
Dimensions according to IEEE Potential tap type A. U
r
= 6 kV
Capacitance C
2
of test tap:
< 5000 pF
Conductor:
Center tube or flexible draw lead conductor.
Markings:
Conforming to IEC/IEEE.
Cenelec Technical specification
50458
Yes, for GSB 245 and GSB 420