Gateway node number “plutoGatewayNode” value of 0 will tell the gateway to read it’s
node number from DIP-switch, see page 19.
•
Additional data configuration of area 00 to get additional data from node 10 (e.g. Pluto
10) with IO-type 111 (e.g. global data), note DN_Path see 19.
•
Additional data configuration of area 01 to get additional data from node 0 (e.g. Pluto 0)
with IO-type 100 (e.g. ToGateway_ErrorCode), note DN_Path see 19.
•
All other additional data is configured as not used e.g. default value of the IO-type is
zero.
It’s good practice to add all additional data setup commands into the configuration file with default
values data area disabled. This will insure that previously used data areas are disabled in the new
configuration, for example insetting old gateway with completely different setup. This also makes it
easier to enable next additional data area if the commands are already there and you only need
too change the default (DefValue) of the new areas.
#
EIO_COMMAND_TYPE:
-Name "plutoInput" -UnitType "plutoGateway" -DefValue "
1
" -OrderNr 1\
-DN_Path "6,20 64 24 00 30 14,C6,1" -DN_Service 16
-Name "plutoOutput" -UnitType "plutoGateway" -DefValue "
1
" -OrderNr 2\
-DN_Path "6,20 64 24 00 30 15,C6,1" -DN_Service 16
-Name "plutoNetEnb" -UnitType "plutoGateway" -DefValue "
3
" -OrderNr 3\
-DN_Path "6,20 64 24 00 30 10,D1,1" -DN_Service 16
-Name "plutoTimeout" -UnitType "plutoGateway" -DefValue "
1000
" -OrderNr 4\
-DN_Path "6,20 64 24 00 30 11,C7,2" -DN_Service 16
-Name "plutoCycleTime" -UnitType "plutoGateway" -DefValue "
100
" -OrderNr 5\
-DN_Path "6,20 64 24 00 30 12,D1,1" -DN_Service 16
-Name "plutoGatewayNode" -UnitType "plutoGateway" -DefValue "
0
" -OrderNr 6\
-DN_Path "6,20 64 24 00 30 13,D1,1" -DN_Service 16
-Name "plutoAddData_Node00" -UnitType "plutoGateway" -DefValue "
10
" -OrderNr 7\
-DN_Path "6,20 64 24 00 30 1E,D1,1" -DN_Service 16
-Name "plutoAddData_IO00" -UnitType "plutoGateway" -DefValue "
111
" -OrderNr 8\
-DN_Path "6,20 64 24 00 30 1F,D1,1" -DN_Service 16
-Name "plutoAddData_Node01" -UnitType "plutoGateway" -DefValue "
0
" -OrderNr 9\
-DN_Path "6,20 64 24 00 30 20,D1,1" -DN_Service 16
-Name "plutoAddData_IO01" -UnitType "plutoGateway" -DefValue "
100
" -OrderNr 10\
-DN_Path "6,20 64 24 00 30 21,D1,1" -DN_Service 16
-Name "plutoAddData_Node02" -UnitType "plutoGateway" -DefValue "
0
" -OrderNr 11\
-DN_Path "6,20 64 24 00 30 22,D1,1" -DN_Service 16
-Name "plutoAddData_IO02" -UnitType "plutoGateway" -DefValue "
0
" -OrderNr 12\
-DN_Path "6,20 64 24 00 30 23,D1,1" -DN_Service 16
-Name "plutoAddData_Node03" -UnitType "plutoGateway" -DefValue "
0
" -OrderNr 13\
-DN_Path "6,20 64 24 00 30 24,D1,1" -DN_Service 16
-Name "plutoAddData_IO03" -UnitType "plutoGateway" -DefValue "
0
" -OrderNr 14\
-DN_Path "6,20 64 24 00 30 25,D1,1" -DN_Service 16