234 Configuration
Configuring STO
To configure the STO function, set the FSO parameters listed below to appropriate
values using the Drive composer pro PC tool. See parameter groups
on
page
on page
.
For more information on the STO and SBC functions, see page
.
Note:
Always set the parameters related to the STO function to have the correct
monitoring limit hit and fault reaction behavior.
How to configure STO
Example:
The figure below shows an example of a simple STO function set-up:
• redundant emergency stop button connected to input
=
DI X113:1 & X114:1
)
• automatic acknowledgement (
=
Automatic
)
• estimated time in which the motor coasts to a stop from the maximum speed is
1500 ms (
Time to zero speed with STO and modoff
=
1500 ms
)
• the fly-start feature is in use, that is, you can restart the drive before the motor has
stopped (
1000 ms
)
• no output connected
• no brake (
=
None
).
= DI X113:1 & X114:1
= None
= None
= None
= 1000 ms
= Automatic
STO activated
Time
= None
Speed
Inputs
Outputs
= 1500 ms
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...