background image

Messages and tests 

 

42 - EN 

FSM4000 

D184B141U02 

 

Warning code and 
ID letter 

Prio-
rity 

Description 

Possible cause 

Corrective action 

Warning: 10  

Reverse Q 

If the flow direction is forward, 
the warning is displayed in case 
of reverse flow. 

Reverse flow 
direction, possibly 
defective check valve. 

Prevent reverse flow or 
change flow direction to 
forward/reverse. 

Warning: 11

2)

 

Poll. Adr. > 0 

12 

The HART unit address was 
changed to an address other 
than zero. The current output 
remains frozen at 4 mA. 

Address 1 ... 15 
selected. The current 
output thereby 
remains set at 4 mA. 

Select 0 as address, if 
the current output 
should be 4 ... 20 mA. 

Warning. 12a

2) 3)

 

Simulation Iout 

13 

Test the current output. Check 
the value displayed at the 
connection terminals using a 
digital voltmeter or the process 
instrumentation. 

Function test, enter 
current output directly 
in mA for simulation. 

Exit the functional test 
of current output. 

Warning. 12b

2) 3)

 

Simulat. Pulse 

14 

Test the pulse output. Check the 
value of output frequency with a 
counter. 

Simulation pulse 
output on. 

Exit the functional test 
of the pulse output. 

Warning. 13

2) 3)

 

Auto. Adjust 

15 

Adjustment started for system 
zero point adjustment via the 
contact input for internal 
adjustment (for ABB Service 
only). 

The external contact 
is closed 

For ABB Service 
personnel only. 

The external contact is 
open again. 

For ABB Service 
personnel only. 

Warning. 14 

Hold MV 

16 

Warning results only when the 
"Noise reduction" function is 
activated. 

Measuring signal 
affected by powerful 
interference signal. 

Set noise reduction to 
lower level or 
deactivate. If 
necessary, contact ABB 
Service. 

Warning F  

Warn. Diagnosis 

17 

Diagnosis or wiring warning 

Min-Max 
over/undershoot for 
diagnostic values. 
Wiring error for 
electrode circuit. Coil 
short-circuit to ground 

Retrieve details of the 
warning message 
under the Status 
submenu in the 
Diagnostic warning 
register. Adjust the limit 
value, if necessary. 

Retrieve details of 
warning message 
under the Status 
submenu in the Wiring 
warning register. 

 

1)

 

Warning is displayed for 30 seconds. 

2)

 

Transmitter must be equipped with HART communication protocol. 

3)

 

Warning is displayed only if the function is called by an external HART protocol command. 

 

Содержание FSM4000 Series

Страница 1: ...D184B141U02 FSM4000 Commissioning Instruction Electromagnetic Flowmeter FSM4000 P R O F I B U S PROCESS FIELD BUS...

Страница 2: ......

Страница 3: ...49 551 905 534 Fax 49 551 905 555 CCC support deapr de abb com Copyright 2008 by ABB Automation Products GmbH Subject to change without notice This document is protected by copyright It assists the us...

Страница 4: ...n on installation 10 3 2 Supports for meter sizes larger than DN 300 10 3 3 Mounting the meter tube 11 3 4 Torque information 12 3 4 1 Flanged flowmeter model SE41F SE21F Wafer flange unit model SE21W...

Страница 5: ...onnection examples for peripherals incl HART 26 5 Startup Operation 28 5 1 Preliminary checks prior to start up 28 5 1 1 Switching on supply power 29 5 2 Commissioning PROFIBUS PA units 30 5 2 1 Infor...

Страница 6: ...the following uses To transmit fluid pulpy or pasty substances with electrical conductivity To measure the flowrate of the operating volume or mass flow units at constant pressure temperature if a ma...

Страница 7: ...A minimum spacing of approx 1 m 3 28 ft should be maintained For installation on or to steel parts e g steel brackets a minimum spacing of approx 100 mm 3 94 inch should be maintained based on IEC801...

Страница 8: ...1 7 Operator liability Before the use of corrosive and abrasive measuring fluid the operator must clarify the resistance of all parts that come into contact with the fluid to be measured ABB will gla...

Страница 9: ...e for the supply power must be installed according to the relevant national and international standards A separate fuse must be connected upstream and in close proximity to each unit The fuses must be...

Страница 10: ...a contact risk The auxiliary power must be switched off before opening the housing cover Warning Risk to persons The inspection screw for draining condensate fluid for devices DN 350 can be under pres...

Страница 11: ...Flanged units may not be lifted by the transmitter housing or terminal box 2 3 Transport of flanged units smaller than DN 350 Warning Danger of injuries due to slipping meter The center of gravity fo...

Страница 12: ...gasket material compatible with hygienic designs Gaskets must not extend into the flow area since possible turbulence could influence the device accuracy The pipeline may not exert any unallowable for...

Страница 13: ...tive plates if present to the right and left of the measuring tube To prevent possible leakage make sure that the liner on the flange is not cut or damaged 2 Position the meter tube coplanar and cente...

Страница 14: ...9 69 62 40 2 100 4 47 77 49 92 67 2 125 5 62 120 76 120 150 6 83 155 96 100 200 8 120 81 120 200 135 170 250 10 97 120 175 320 135 185 300 12 115 160 175 340 180 265 350 14 145 195 280 2 2 2 400 16 20...

Страница 15: ...ertically with the terminal box or transmitter housing pointing downward G00528 Fig 5 The bracket mounting option no longer applies G00529 1 Fig 6 1 Bracket Please ensure that the leakage hole of the...

Страница 16: ...the outlet pipe section 2 For compliance with the measuring accuracy observe the inlet and outlet pipe sections G00037 1 2 3xDN 2xDN Fig 10 3 6 3 Vertical connections Vertical installation for measur...

Страница 17: ...ning the ground is provided by the grounding plate or grounding electrodes When stray potentials are present install a grounding plate at the front and back of the flowmeter sensor For measurement rel...

Страница 18: ...bber lining For devices with meter sizes DN 125 and larger the liner contains a conductive element This element grounds the measuring agent 3 7 7 Ground for devices with protective plates The protecti...

Страница 19: ...able D173D147U01 Preparing the transmitter side G00535 15 5 30 1 18 8 8 80 3 15 60 2 36 0 20 0 59 17 0 67 0 31 17 0 67 0 31 Preparing the flowmeter sensor side G00549 5 4 3 2 1 G00552 M1 M3 1 2 3 Cabl...

Страница 20: ...g pulses and induction If this is not possible run the signal magnet coil cable through a metal pipe and connect this to the station ground All leads must be shielded and connected to station ground D...

Страница 21: ...ze and width G00553 SE SE 3A 3A 1S 2S 1 2 3 16 16 M1 M3 1 2 3 6 5 7 4 6 9 8 G00554 SE SE 3A 3A U U 1 2 3 16 16 M1 M3 1 2 3 6 5 7 4 6 9 8 Fig 22 1 red 2 blue 3 yellow 4 white 5 black 6 SE clamp 7 Signa...

Страница 22: ...r sensor and the transmitter 2 Connect the signal cable in the terminal box of the flowmeter sensor 3 Route the cable from the terminal box to over the maximum flooding height of 5 m 4 Tighten the cab...

Страница 23: ...he installation before beginning sealing activities in order avoid moisture penetration Before starting check all the connections for correct fitting and stability Do not overfill the terminal box Kee...

Страница 24: ...sign with a fluid temperature of max 180 C the connection box for sizes DN 125 5 and larger is separated from the lower section of the flowmeter sensor by a piece of pipe This provides complete therma...

Страница 25: ...able shielded 2 x 1 mm2 CE Typ 227 TEC 74 ABB order no D173D147U01 10 m included in shipment standard 7 Supply power Low voltage 100 230 V AC terminals L N Low voltage 20 4 26 4 V AC Low voltage 20 4...

Страница 26: ...rminals 1 2 Frequency 47 Hz f 53 Hz 50 Hz supply power Frequency 56 Hz f 64 Hz 60 Hz supply power 8 Steel shielding 9 Aluminum foil 10 Yellow 11 Shield 12 Blue 13 Red 14 white 15 Shielded signal cable...

Страница 27: ...nnection via M12 plug in the operating 3a instructions and or data sheet 3c Bus termination with installed bus termination 3a components with hook switches closed 4 Magnet coil cable shielded 2 x 1 mm...

Страница 28: ...0 V 24 V DC Note Horn and alarm light are shown only as examples Other suitable devices such as bells sirens buzzers etc can also be used Contact output selectable in software Function Passive closed...

Страница 29: ...ive optocoupler PROFIBUS PA FOUNDATION Fieldbus G00248 2 FF FF R C 1 97 PA R C PA 98 97 98 I E I E The resistance R and condenser C form the bus termination They must be installed when the device is c...

Страница 30: ...The data module stores the sensor data e g size Cs Cz type etc as well as the setup data on the transmitter after commissioning Prior to commissioning plug the external FRAM for the appropriate sensor...

Страница 31: ...e passive jumper inner B Pulse active jumper outer Important The transmitter is immediately ready for operation after mounting and installation of the connections The parameters are set at the factory...

Страница 32: ...nit via the DIP switches on the digital board using system tools or via a PROFIBUS DP master class 2 such as SMART VISION DSV401 The factory setting for DIP switch 8 is OFF i e the address is set usin...

Страница 33: ...h Switches 1 5 7 ON means 1 16 64 81 Bus address 81 Switch 1 2 3 4 5 6 7 8 9 A Status Unit address Address mode no function no function Off 0 0 0 0 0 0 0 Bus no function no function On 1 2 4 8 16 32 6...

Страница 34: ...selector is preconfigurd with the ID no 0x078C hex The IDs 0x9700 or 0x9740 can also be used 5 2 1 Information on voltage current consumption Da sEinschaltverhalten entspricht dem Entwurf DIN IEC 65C...

Страница 35: ...ION fieldbus the settings of the DIP switch must be checked prior to commissioning When integrating the unit in a process control system a DD file device description and a CFF file common file format...

Страница 36: ...ddress settings The bus address is automatically allocated at the FF via LAS link active scheduler For address detection a unique number is used DEVICE_ID This number is a combination of manufacturer...

Страница 37: ...ctions of the individual keys are explained in the following C CE Toggle between operating mode and menu STEP The STEP key is one of two arrow keys Use STEP to scroll forward through the menu All the...

Страница 38: ...r more than 3 seconds The display flashes to indicate that the function is active There are two different methods of entering data Numeric entry Entry from specified table Important When entering data...

Страница 39: ...STEP or DATA 1800 00 m h 5 Parameter Submenu unit STEP or DATA Unit Qmax Unit Qmax 6 Change parameter Qmax ENTER m h 6 Change parameter m h ENTER m h Min 500 m h Max 10000 m h Unit Qmax 7 Find desire...

Страница 40: ...Qmax l s Unit totalizer m3 Qmax 50 000 l s Damping 1 Tau 0 22 sek Display mode 4 small Display 1st line Q Unit Display 2nd line Display 4th line Display 3rd line Within Easy Set up call up the next p...

Страница 41: ...he DSP board Error 2 Driver 7 Positive or negative reference too small Check the cables no reference voltage is present The current limiter in the driver has responded because the driver current is in...

Страница 42: ...signal Empty pipe Activate Noise reduction in the operating mode submenu Use a air separator clean electrodes activate empty pipe detector Contact ABB Service Error F FRAM in Primary 1 Missing data fr...

Страница 43: ...cognized different flowmeter sensor data and loaded it in the internal FRAM Loaded are the system and flowmeter sensor data Defective FRAM repair unit replace instrument Write down all totalizer value...

Страница 44: ...with a counter Simulation pulse output on Exit the functional test of the pulse output Warning 132 3 Auto Adjust 15 Adjustment started for system zero point adjustment via the contact input for intern...

Страница 45: ...th HART communication D184B126U01 02 Interface Description for devices with PROFIBUS PA communication D184B093U29 30 Interface Description for devices with PROFIBUS Fieldbus communication D184B093U31...

Страница 46: ...Appendix 44 EN FSM4000 D184B141U02...

Страница 47: ...Appendix D184B141U02 FSM4000 EN 45...

Страница 48: ...Appendix 46 EN FSM4000 D184B141U02...

Страница 49: ......

Страница 50: ...ein without notice Printed in the Fed Rep of Germany 09 2008 ABB 2008 D184B141U02 ABB Limited Oldends Lane Stonehouse Gloucestershire GL10 3TA UK Tel 44 0 1453 826661 Fax 44 0 1453 829671 ABB Inc 125...

Отзывы: