26 Electrical installation
Installation procedure
1. Stop the drive and do the steps in section
on page
before you start the work.
2. Connect the power supply cables to the X81 terminal.
3. Connect the safety encoder to the X31 terminal as follows:
Note
: This diagram is applicable to all revisions of FSE-31.
However, VCC is 15 V DC for revision F and later, and 24 V
DC for the module revisions A to E. You can see the revision of
the module on the type designation label. Refer to
on page
.
4. Make sure that the electrical installation is completed. See
chapter
Installation checklists
in the
FSO-21 safety functions
module user’s manual
(3AXD50000015614 [English]).
WARNING!
Use only the X31 connector of the FSE-31
module to supply power to the encoder. Do not use other
power supplies, because they can cause damage to the
module.
1
1
0
VCC 0V
2
FSE-31
B+
B-
Z+
Z-
SHLD
2
0
3
4
5
6
7
8
A-
A+
9
X31
Encoder 1
COM_ENC
VCC_ENC
2