30
Maintenance
To activate reduced run:
1. Stop inverter operation with the Start/Stop switch or with the parameter
189.01 Inverter
operation
.
2. To access the reduced run control parameters, enter an engineer level passcode to
parameter
196.02. Passcode
.
3. Select a power section to be disabled with the applicable parameter:
•
206.2 Power section 1 forced disable
•
206.3 Power section 2 forced disable
4. Verify the status of the active power sections with parameter
206.1 Power section
status
. A value of “1” means that the power section is in use.
5. Restart the inverter. Turn the Start/Stop switch to position 1 and set the parameter
189.01 Inverter operation
to Enable. The inverter automatically closes the AC
breakers in the active power sections and always from power section 1.
6. The inverter automatically controls the AC and DC contactors of the active power
sections. The contactors in the disabled power sections are commanded to open and
their status must be open.
Note:
•
The power sections are numbered 1…n. The power section closest to the
inverter’s control section is number 1.
•
The manual AC switch or breaker of power section 1 must always be closed
when the inverter operates, even in reduced run mode, since the AC grid voltage
measurement is taken from between the AC main fuses and the AC contactor of
power section 1.
•
If the power section to be disconnected is other than power section 1, you can
open the optional manual AC switch for additional isolation from the AC grid.
•
The optional AC breaker of the power section 1 is controlled by software, even
if that power section operation is disabled.
Содержание Fimer PVS980-58-1818kVA-I
Страница 1: ...Central inverter PVS980 58 From 1818 to 2091 kVA Commissioning and maintenance manual ...
Страница 4: ...2 ...
Страница 14: ...12 Safety instructions ...
Страница 18: ...16 Introduction to the manual ...
Страница 28: ...26 Electrical commissioning ...
Страница 60: ...58 Maintenance ...
Страница 61: ...Further information For more information on FIMER products and services for solar applications visit fimer com ...