![ABB FAIO-01 Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/abb/faio-01/faio-01_user-manual_2711027.webp)
■
Analog inputs and outputs
Connector pitch 5 mm, wire size max. 2.5 mm
2
Analog inputs
(XAI1:+1…-2,
XAI2:+3…-4)
Input ranges: (-20) 0…20 mA (default), (-2) 0…2 V, (-10)
0…10 V
Input impedance: 100 ohm (current), ≥ 200 ohm (voltage)
Inaccuracy: ±0.2% of input and ±0.1% of Full Scale
Range at 25 °C
Inaccuracy for Pt100 sensors: 5 °C (9 °F)
Basic insulation against the control unit ground (earth):
functional insulation against the analog outputs
Common mode rejection rating (CMRR): ±15 V
Hardware filtering time constant: 0.2 ms
Connector pitch 5 mm, wire size max. 2.5 mm
2
Analog outputs
(XAO1:+5…-6,
XAO2:+7…-8)
Output range: 0…20 mA
Load resistance max.: 700 ohm
Inaccuracy: ±0.2% of output and ±0.1% of Full Scale
Range at 25 °C
Basic insulation against the control unit ground (earth):
functional insulation against the analog inputs
■
Power supply
+3.3 V and 24 V (supplied by the drive control unit or
the FEA-03 extension adapter module)
Analog outputs
(XAO1:+5…-6,
XAO2:+7…-8)
Max. power consumption: 50 mA at 3.3 V, 0.3 A at
24 V
■
General
•
Complies with standards EN 61800-3, EN 61800-5-1, UL508C
•
CULus listed
•
Printed circuit board conformal coated
Technical data 27