![ABB FAIO-01 Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/abb/faio-01/faio-01_user-manual_2711022.webp)
Setting the parameters
The extension module is started up through drive parameters. For
example, in ACS880 Primary control program the parameters for I/O
extension modules are located in parameter groups 14...16. For other
programs, see the applicable firmware manual.
■
Example – Primary control program
1. Power up the drive.
2. Specify the slot into which the extension module is installed on
the drive control unit (
14.02 Module 1 location
).
3. Activate the communication between the extension module and
the drive (
14.01 Module 1 type
).
You can now see the parameters of the extension module in
group 14.
4. Make sure that the drive finds the correct extension module (
14.03
Module 1 status
)
5. Set the parameters of the extension module to applicable values.
The settings must correspond to the DIP switch settings and the
wiring of the extension module.
6. If you want to use an input of the extension module as a signal
source, choose the setting
Other
in the source selector parameter,
and then specify the applicable value parameter in group 14.
Example: To connect supervision 1 to AI1 of the extension
module:
•
Select the mode of the supervision function (
32.05
Supervision function 1
).
•
Set limits for the supervision function (
32.09 Supervision 1
low
and
32.10 Supervision 1 high
).
•
Select the supervision action (
32.06 Supervision 1 action
).
•
Connect
32.07 Supervision 1 signal
to
14.27 AI1 scaled value
.
7. Set the rest of the required drive parameters to applicable values.
For more detailed information on the parameters, see the drive
firmware manual.
22 Start-up