ABB EQmatic
Commissioning
48 2CDC512090D0202 | QA/S x.yy.1
3.2.3.1
Manual structure
The manual structure allows you to set up a custom topology. With a manual structure, physical
meters are assigned to a logical metering structure. This structure can be used, for example, to
show consumption figures and costs for a cost center or organization. The
virtual meter
and
metering point
structural elements are provided for this purpose.
Virtual meter (group)
A virtual meter summarizes consumption and/or measurement data from meters assigned below
the first level in the tree structure. Data points or values that can be physically added together (e.g.
energy in kWh, power in W) are added together in the root node. This means that you can display
the overall consumption and costs for all the sub-meters via the root node.
A meter cannot be assigned directly to a virtual meter.
Example (see graphic/screenshot):
Total 1.0 = 1.1 + 1.2
500 kWh = 350 kWh + 150 kWh
Metering point
A metering point only ever consists of one M-Bus device which is assigned to it. The relevant
medium for the assigned M-Bus device is represented by a symbol (see: Medium).
If a higher-level metering point is serving as a primary meter, the nodes assigned below it must
belong to the same medium.
Содержание EQmatic
Страница 1: ... PRODUCT MANUAL EQmatic Energy Analyzer M Bus Energy Analyzer Modbus ...
Страница 9: ......
Страница 13: ...ABB EQmatic Device technology 12 2CDC512090D0202 QA S x yy 1 Dimension drawing QA S 3 xx 1 2CDC072033F0015 ...
Страница 17: ...ABB EQmatic Device technology 16 2CDC512090D0202 QA S x yy 1 Dimension drawing QA S 4 xx 1 2CDC072033F0015 ...
Страница 95: ......
Страница 105: ......