ABB EQmatic
Commissioning
QA/S x.yy.1 | 2CDC512090D0202 29
Scan configuration
Options:
Primary
Secondary
The M-Bus first needs to be scanned for the Energy Analyzer to detect connected devices. This
scanning process uses either primary or secondary addressing.
Primary
: If you select this option, the search for devices connected is based on their primary
address. The primary addresses must be set beforehand on the relevant device (M-Bus slave).
Note
The primary address is pre-set to 0 on ABB meters in the factory.
Each M-Bus device must be assigned a unique primary address. Duplicate addresses cause address
conflicts!
Speed range (baud rate)
Options:
300, 600, 1200, 2400, 4800, 9600
Sets the speed range used for scanning for M-Bus devices connected. Communication with M-Bus
devices is only in this range. The speed range set here must match the speed set on the M-Bus
slave. Otherwise the system cannot detect any devices. The speed can be set based on meter
type.
Note
ABB meters are supplied from the factory with the speed 2400.
You should limit the scan range as much as possible. The wider the speed range, the longer the
scanning process takes.
Address range
Options:
1…250
Sets the limits for the primary address range. This parameter is only visible if
Primary
is selected.
Note
The wider the range, the longer the scanning process takes.
Содержание EQmatic
Страница 1: ... PRODUCT MANUAL EQmatic Energy Analyzer M Bus Energy Analyzer Modbus ...
Страница 9: ......
Страница 13: ...ABB EQmatic Device technology 12 2CDC512090D0202 QA S x yy 1 Dimension drawing QA S 3 xx 1 2CDC072033F0015 ...
Страница 17: ...ABB EQmatic Device technology 16 2CDC512090D0202 QA S x yy 1 Dimension drawing QA S 4 xx 1 2CDC072033F0015 ...
Страница 95: ......
Страница 105: ......