Considering 4000A as a rated current (In) , fans will activate when the current croses 3600
amps & will stop if the curret drops below 3400 amps.
Figure 68
The current thresholds allow you to set controls on current lines, to be combined with the
programmable contacts of the Ekip Signalling modules.
Two pairs of programmable contacts are available:
Threshold 1 I1 and Threshold 2 I1, with control referred to I1
Threshold Iw1 and Threshold Iw2, with control referred to In
For Fan control configure Iwi and Iw.
36 - Configuring threshould currents for Fan control