4CAE000359
Disturbance Recording and Fault Locating Device DRL6600U
Product version: V8.30
Issued: May 2017
Revision: -
19
ABB
Table 9: Signal output
Description
Reference value
Rated voltage
250V DC/AC
Continuous current-carrying capacity
5A
3 seconds current-carrying capacity
10A
0.5 second current-carrying capacity
30A
Table 10: Data communication Ethernet port
Ethernet port
Protocol
Cable
Data transfer rate
LAN/LHMI port (X0), only for external LHMI
-
RJ-45
100MBits/s
LAN1(X1)
TCP/IP
RJ-45
100MBits/s
Table 11: IRIG-B port
Type
Protocol
Cable
Screw terminal, pin row
header
IRIG-B
Shielded twisted pair
Recommendation: CAT 5, Belden RS-485 (9841-
9844) or Alpha electric wire (Alpha 6222-6230)
Table 12: IP classification, flush mounting
Description
Value
IED front panel
IP 40
IED back panel, connecting terminal
IP 20
DRL6600U-HMI front panel and side
IP 40
Table 13: Ambient conditions
Description
Reference value
Operation temperature range
-10...+55ºC (continuous)
Short-time service temperature range
-25…+70ºC(<16h)
Relative humidity
<93%, no moisture condensation
Atmospheric pressure
86...106 kPa
Altitude
Maximum 2000m
Transport and storage temperature range
-40...+70ºC