Voltage
Monitors
Low Voltage Products & Systems
7.9
ABB Inc. • 888-385-1221 • Technical assistance 800-377-7722 • www.ssac.com
1TRC 001 009 C0202
Technical Data
Universal 3 Phase Voltage Monitor
HLMU Series (DPDT)
Motor Protector
Mechanical View
HLM02B01 11.21.06
Inches (Millimeters)
-Hole for Mounting with One #10 (M4 x 0.7) Screw
Cover Detail
Knobs & Dials
(Fully adjustable
Part Numbers)
Line Voltage
Type
3 phase Delta or Wye with no connection to neutral
Operating Voltage
200 ... 480 V AC Range Voltage Adjustment Range Line Frequency
Line Voltage Max.
550 V AC
Line Frequency
50 or 60 Hz Automatically detected
Phase Loss
≥
25% Unbalance
Response Time
≤
200ms
Undervoltage and Voltage Unbalance
Type
Voltage detection with delayed trip & automatic reset
Overvoltage:
109 to 113% of the adjusted line voltage
≅
-3% of the trip voltage
Undervoltage:
88 ... 92% of the adjusted line voltage
≅
+3% of the trip voltage
Voltage Unbalance:
Adjustable 2 ... 10%; or specify fixed unbalance of 2 ... 10% in 1% increments
≅
-0.7% Unbalance
Trip Delay
Over/Undervoltage, Voltage Unbalance, Over/Under Frequency
Adjustable from 1 ... 30 s; or specify fixed delay 1 ... 30 s in 1 s increments
± 15%
Restart Delay
Adjustable from 0.6 ... 300 s; if no restart delay is selected a 0.6 s initialization delay applies
± 15%
Over/Under Frequency
±4%; Reset ±3%; 50 or 60 Hz
Phase Sequence
A, B, C, L1, L2, L3
Response Time-Phase Reversal
& Phase Loss
≤
200 ms
Reset
Automatic
Output
Type
Isolated Electromechanical Relay
Form
Double pole double throw (DPDT)
Rating
10 A resistive at 240 V AC; 8 A resistive at 277 V AC; N.O-1/4 hp at 120 V AC; 1/3 hp at 240 V AC;
Life
Mechanical -- 1 x 10
6
Electrical -- (at 10 A) -- DPDT = 1 x 30
3
Protection
Surge
IEEE C62.41-1991 Level B
Isolation Voltage
≥
2500 V RMS input to output
Circuitry
Encapsulated
Mechanical
Mounting
Surface mount with one #10 (M5 x 0.7) screw
Note: 0.25 in.(6.35 mm) spacing between units or other devices is required
Package
3 x 2 x 1.5 in. (76.7 x 51.3 x 41.7 mm)
Termination
Screw terminal connection for up to 12 AWG (3.3 mm
2
) wire
Environmental
Operating Temperature
-40°C ... +60°C
Storage Temperature
-40°C ... +85°C
Humidity
95% relative, non-condensing
Weight
≅
3.9 oz (111 g)
240 200 ... 240 V AC
50 or 60 Hz
380 340 ... 420 V AC
50 Hz
480 400 ... 480 V AC 60 Hz
Trip Voltage
Reset Voltage
Trip Voltage
Reset Voltage
Trip Set Point
Reset on Balance
Active On
Range
Tolerance
Range
Tolerance
Trip / Reset