DCS800 Firmware manual supplement for North America (rev. 2.60, 2.70)  Rev. b 

5/30/2008 

3

 
 

Revision Information 

This supplement is dedicated to 

Revision 2.6 and Revision 2.7

 of the DCS800 Firmware.  

Drives shipped after March, 2008 will most likely have this revision. 
 
 

What revision do I have? 

To determine your firmware revision number, check the value of signal: 

FirmwareVer (4.01)

 

Or check the label on the box: 
 

 

 

 

 

 
 

What’s different with this revision 

1.

 

New Macros: Four new macros have been added.  See details later in this 
supplement. 

2.

 

Date display in control panel data logger:  The data logger now correctly displays the 
date and time of the fault. 

3.

 

Autotuning field current controller assistant:  Autotuning now works when both field 
exciters are enabled. 

4.

 

Nuisance A131 ParAdded:  This alarm was seen sometimes after drive is energized.  
This has now been corrected. 

5.

 

RdyOn with RDIO:  When energizing the drive and using a RDIO, the signal RdyOn 
(

MainStatWord

 8.01) came on too early.   

6.

 

DC Voltage Measurement:  Overflow protection has been added.  This was needed 
for electromagnet control. 

7.

 

DC Nom Current:  A fault is now set when M1NomCur (99.03) is set to zero. 

8.

 

Autotuning Speed Controller:  This autotune tripped when M1MinSpeed (20.01) or 
M1MaxSpeed (20.02) was set to zero.  This has now been corrected. 

9.

 

Bumpless transition:  When changing torque selector (26.01) from MIN/MAX to 
SPEED, you will now see a bumpless transition. 

Indicates Revision 2.6 

Содержание DCS800

Страница 1: ...1 DCS800 Firmware manual supplement for North America Firmware Rev 2 60 and Rev 2 70 DCS800 Drives 20 to 5200 A ABB...

Страница 2: ...vision do I have What s different with this revision Introduction 4 Macros 4 Macro configuration tables 5 6 DC contactors with without dynamic braking 8 AC contactors 10 Field heating 11 Saving and re...

Страница 3: ...te and time of the fault 3 Autotuning field current controller assistant Autotuning now works when both field exciters are enabled 4 Nuisance A131 ParAdded This alarm was seen sometimes after drive is...

Страница 4: ...e a macro has been implemented these designations are easily changed For many a macro is a starting point it may also be the end point but it is not necessarily so Revised macros in rev 2 6 and above...

Страница 5: ...d 5 DO5 Above limit Above limit Above limit Above limit At Setpoint 6 DO6 7 DO7 8 0 V 1 2 Factory macro Resets all parameters to default values Drive turns on with maintained input Motion is commanded...

Страница 6: ...ing ReadyRef running ReadyRef running 3 DO3 Fault or alarm Fault or alarm Fault or alarm Fault or alarm Fault or alarm 4 DO4 Zero speed ZeroSpeed Zero speed Zero speed Zero speed 5 DO5 DC breaker trip...

Страница 7: ...enable with this method After connecting to the drive with DriveWindow Light see Quick Guide for details click on the wizard Then select the checkbox next to 2 Macro Assistant Then select Next At the...

Страница 8: ...put contactor is used A single pole NO DC contactor is used for dynamic braking When dynamic braking is required the AC contactor is opened removing power to the drive and the DC contactor is closed c...

Страница 9: ...he drive for dynamic braking The drive allows you to select the stopping method under three different situations Parameters 21 02 21 03 and 21 04 select the stopping method for loss of the OnOff run c...

Страница 10: ...tion See the DCS800 firmware manual Page 120 group 6 parameters Drive Logic Signals Page 168 group 14 parameters Digital Outputs Pages 180 181 group 21 parameters Start Stop Pages 205 207 group 30 par...

Страница 11: ...ld was left on to keep it warm Then the voltage controlled field supply would work just fine The new generation of drives including all field supplies used with the DCS800 are current controlled meani...

Страница 12: ...reduced On On On Field On On or Off On On Off Field will turn off safely as motor coasts to stop and cannot turn back on again until Off2 is switched on while OnOff and Run are off All other condition...

Страница 13: ...by clicking on File then New Online Drive 2 Click on File then Open in Browser Find the desired dwp file Then click OPEN 3 A message will appear stating You are opening a new file in OnLine Mode All v...

Страница 14: ...e this function appears 2 The function DOWNLOAD APPLICATION is currently not available For additional information See the DCS800 firmware manual Page 272 280 DCS800 panel operation Page 279 Parameter...

Страница 15: ...le the block is toggling bit 11 of the MainCtrlWord 7 01 according to the state of 84 09 0 leaving the other MainCtrlWord bits as they were before The modified copy of the MainCtrlWord is written to p...

Страница 16: ...Light 1 Connect to the DCS800 and go on line by clicking on File then New Online Drive 2 Click on Wizard on the left side of the screen 3 Click on Advanced 4 Check the box for I O assistant then clic...

Страница 17: ...NotUsed DI 4 14 01 603 801 801 801 801 801 14 02 0 1 1 0 0 1 14 03 603 801 801 801 801 801 14 04 5 2 2 2 2 10 14 05 603 802 801 801 801 802 14 06 7 13 3 3 3 13 14 07 0 802 802 802 802 802 14 08 0 11 1...

Страница 18: ...2 802 802 802 802 14 06 13 13 13 13 13 14 07 802 802 802 802 802 14 08 11 11 11 11 11 14 09 603 801 801 801 801 14 10 15 10 10 10 10 14 16 7 7 10 10 7 15 01 104 104 104 104 104 15 06 108 113 113 113 1...

Страница 19: ...DCS800 Firmware manual supplement for North America rev 2 60 2 70 Rev b 5 30 2008 19 Notes...

Страница 20: ...DCS800 Firmware manual supplement for North America rev 2 60 2 70 Rev b 5 30 2008 20...

Отзывы: