10
D1M 20
POWER METER USER MANUAL
10
Voltage measurement inputs
Voltage input mode
Direct or Indirect insertion with VT
Measurement Range
80-300 VAC(L-N)
Wiring Type
Single-phase, three-phase (3P, 3P+N)
Rated frequency
50Hz or 60Hz
VT primary range
50~750000V
VT secondary range
50~510V
Individual harmonics
2nd~40th, 0%~50%
Current measurement inputs
Current input mode
Indirect insertion with CT
Wiring Type
Single-phase, three-phase (3P, 3P+N)
CT secondary range
1A or 5A
Rated frequency
50Hz or 60Hz
Range without accuracy derating
50mA-5A AC 120%
CT primary range
1-50000A
Wiring Type
Single-phase, three-phase (3P, 3P+N)
Individual harmonics
2nd~40th, 0%~50%
Digital Input
Number of channels
2
Voltage
24 VDC
Frequency
<1kHz
Digital Output
2
Number of channels
2
Voltage
24 VAC/DC
Current
≤100mA DC
Width
10 ~ 990ms
Mechanical properties
Overall Dimensions
89.0mm x 52.5mm x 63.5mm
IP degree of protection (IEC 60529)
Front: IP51
Terminals: IP20
Max. weight
259g
Fireproof and Heatproof
Terminal 960°C, cover 650°C
Climatic conditions
Operating temperature
-5 to 55°C (K55 IEC61557-12)
Storage temperature
-25 to 70°C (K55 IEC61557-12)
Relative humidity
≤75% yearly average
≤95% on 30 days/year
Altitude
≤2Km
Pollution degree
2
Environment
It is prohibited to use in the environment containing
H2S, Cl2, NH3 and other harmful gases
Communication protocol
Modbus RTU
D1M 20 Modbus
Communication interface
RS485 with optical isolation
Baud rate
9.6, 19.2, 38.4, 57.6, 115.2 kbps
Parity number
Odd (1 stop bit), Even (1 stop bit), None (1 stop bits)
Address
1-247
Connector
3 pole terminal