9
D1M 15
MULTIMETER USER MANUAL
9
3.5.Technical data
Auxiliary power supply
Voltage range
100-230 V AC/DC ±15%
Frequency
50 - 60Hz ±5%
Power Consumption
5VA max
Installation category
CAT III 300V class per IEC 61010-1 edition 3
Protection fuse
T1 A-277 VAC
Measurement accuracy
IEC 61557-12
IEC 61557-12 PMD/S/K55/1
Active energy
IEC61557-12 Class 1
IEC 62053-21 Class 1
Reactive energy
IEC 61557-12 Class 2
IEC 62053-24 Class 2
Active power
IEC 61557-12 Class 1
Reactive power
IEC 61557-12 Class 2
Apparent power
IEC 61557-12 Class 2
Voltage
IEC 61557-12 Class 0.5
Current
IEC 61557-12 Class 0.5
Frequency
IEC 61557-12 Class 0.1
Voltage measurement inputs
Voltage input mode
Direct or Indirect insertion with VT
Voltage Range
80-300 VAC(L-N)
Wiring Type
Single-phase, three-phase (3P, 3P+N)
Rated frequency
50Hz or 60Hz
Protection fuse
T1 A-277 VAC
VT primary range
50~750000V
VT secondary range
50~510V
Current measurement inputs
Current input mode
Indirect insertion with CT
Rated current at secondary side of CT
1A or 5A
Rated frequency
50Hz or 60Hz
Range without accuracy derating
50mA-5A AC 120%
CT primary range
1-50000A
Wiring Type
Single-phase, three-phase (3P, 3P+N)
I/O
Digital Output
Number of channels
2
Voltage
40V DC
Current
≤60mA DC
Width
10 ~ 990ms
Mechanical properties
Overall dimensions
89.0mm x 52.5mm x 63.5mm
IP degree of protection (IEC 60529)
Front: IP51 @ IEC 60529
Enclosure: IP20 @ IEC 60529
Weight
252g
Fireproof and Heatproof
Terminal 960°C, cover 650°C @IEC 60695-2-1-UL V0
Содержание D1M 15
Страница 1: ...MULTIMETER D1M 15 User manual D1M 15 User manual 9AKK108468A5637...
Страница 2: ......
Страница 11: ...11 D1M 15 MULTIMETER USER MANUAL 11 4 Installation 4 1 Assembly 4 2 Disassembly 1 1 2 2...
Страница 49: ......