MULTIMETER USER MANUAL

1. General information

1.1.Use and storage of manuals

Carefully read this manual and adhere to the indications described prior to using the device.

This manual contains all of the safety information, the technical aspects and the operations necessary to 

ensure the correct use of the device and maintain it in safe conditions.

1.2.Copyright

The copyright of this manual is the property of 

ABB LV Installation Materials Co. Ltd. Beijing

. This manual 

contains texts, designs and illustrations of a technical nature which must not be disclosed or transmitted 

to third parties, even partially, without the written authorization of 

ABB LV Installation Materials Co. Ltd. 

Beijing

.

1.3.Liability disclaimer

The information contained in this document is subject to change without notice and cannot be 

considered as an obligation by 

ABB LV Installation Materials Co. Ltd. Beijing. ABB LV Installation 

Materials Co. Ltd. Beijing

 is not liable for any errors that may appear in this document. 

ABB LV 

Installation Materials Co. Ltd. Beijing

 is not liable under any circumstances for any direct, indirect, 

special, incidental or consequential damage of any kind that may arise from using this document. 

ABB LV 

Installation Materials Co. Ltd. Beijing

 is also not liable for incidental or consequential damage that may 

arise from using the software or hardware mentioned in this document.

1.4.General safety warnings

Non-adherence to the following points can lead to serious injury or death.

Use the suitable personal protection devices and adhere to the current regulations governing electrical 

safety.

•  This device must be installed exclusively by qualified personnel who have read all of the information relative 

to the installation.

•  Check that the voltage supply and measurement are compatible with the range permitted by the device.
•  Ensure that all current and voltage supplies are disconnected prior to carrying out any controls, visual 

inspections and tests on the device.

•  Always assume that all circuits are under voltage until they are completely disconnected, subjected to tests 

and labelled.

•  Disconnect all of the power supply prior to working on the device.
•  Always use a suitable voltage detection device to check that the supply is interrupted. 
•  Pay attention to any dangers and carefully check the work area ensuring that no instruments or foreign 

objects have been left inside the compartment in which the device is housed.

•  The correct use of this device depends on a correct manipulation, installation and use.hdfh.
•  Failure to adhere to the basic installation information can lead to injuries as well as damage to the electric 

instruments or to any other product.

•  NEVER

 connect an external fuse in by-pass.

•  Disconnect all of the input and output wires before carrying out a dielectric rigidity test or an insulation test 

on an instrument in which the device is installed.

•  The tests carried out at a high voltage can damage the device’s electronic components.
•  The device has to be installed on a standard 35mm DIN rail. 
•  Installation of D1M shall include a switch or circuit breaker for the connection of auxiliary supply and voltage 

measurement. The switch or circuit breaker must be suitably located and easily reachable and must be 

marked as the disconnecting device for D1M. 

•  Before connecting the auxiliary power supply and voltage measurement, or disconnecting the auxiliary 

power supply or voltage measurement, you must turn off the circuit breaker or switch.

Содержание D1M 15

Страница 1: ...MULTIMETER D1M 15 User manual D1M 15 User manual 9AKK108468A5637...

Страница 2: ......

Страница 3: ...3 2 Main functionalities 8 3 3 Versions 8 3 4 Overall dimensions 8 3 5 Technical data 9 4 Installation 11 4 1 Assembly 11 4 2 Disassembly 11 4 3 Wiring diagrams 12 5 Access to device 14 5 1 Display 14...

Страница 4: ...4 D1M 15 MULTIMETER USER MANUAL 8 Data reading RED 39 8 1 Realtime REAL 40 8 2 Energy ENRG 41 8 3 Power Quality PWQT 42 8 4 I O 43 8 5 Notifications NTF 44 8 6 Power Outage PWF 47 9 Conclusion 48...

Страница 5: ...xclusively by qualified personnel who have read all of the information relative to the installation Check that the voltage supply and measurement are compatible with the range permitted by the device...

Страница 6: ...r damages and or losses related to such security breaches unauthorized access interference intrusion leakage and or theft of data or information D1M products can only work on a Local Area Network it u...

Страница 7: ...7 D1M 15 MULTIMETER USER MANUAL 2 Packaging contents Packaging contents 1 Multimeter D1M 15 2 Installation manual 3 Calibration certificate 1 2 3...

Страница 8: ...cts are perfectly suitable for ABB electrical systems and solutions 3 2 Main functionalities Real time Measurement TRMS Current TRMS Voltage Frequency Active Reactive and Apparent Power Power Factor E...

Страница 9: ...ement inputs Voltage input mode Direct or Indirect insertion with VT Voltage Range 80 300 VAC L N Wiring Type Single phase three phase 3P 3P N Rated frequency 50Hz or 60Hz Protection fuse T1 A 277 VAC...

Страница 10: ...er harmful gases Communication protocol Modbus RTU D1M 15 Modbus Communication interface RS485 with optical isolation Baud rate 9 6 19 2 38 4 57 6 115 2 kbps Parity number Odd 1 stop bit Even 1 stop b...

Страница 11: ...11 D1M 15 MULTIMETER USER MANUAL 11 4 Installation 4 1 Assembly 4 2 Disassembly 1 1 2 2...

Страница 12: ...ith the voltage detection device D1M 15 D1M 15 Mobdus Type of network D1M 15 can be used on different type of network please refer to chapter 7 Configuration CFG for the configuration on the device Ac...

Страница 13: ...3P3W2CT Aux 3 phase 3 wire network with 1CT 3 1T PE L1 A L2 B L3 C I1 S1 I2 I3 S2 S1 S2 S1 S2 L1 L2 L3 N Voltage 3P3W1CT Aux PE PE L1 A L2 B L3 C I1 S1 I2 I3 S2 S1 S2 S1 S2 L1 L2 L3 N Voltage 3P3W1CT...

Страница 14: ...ng how to read data and configure related parameters 5 1 Display Front panel D1M 15 products use LED displayer the front panel of D1M 15 is shown below Operator panel 1 Display area 2 Function buttons...

Страница 15: ...ve load or the negative sign 3 Measurements Specific measured value or other contents 4 Magnitude Magnitude includes K M and G 5 Icons Indicating various types of state and for further details see the...

Страница 16: ...onfiguration read only 5 3 Data entry Some of the pages require the entry of numerical characters 0 9 in the Configuration mode In these cases the display will show an active field identified by a fla...

Страница 17: ...l characters from 0 to 9 until the required character is obtained How to Go back to a previous number If during the data entry the desired number is exceeded by mistake it is needed to increase the di...

Страница 18: ...tering the comma Comma can be displayed by increasing the number with Up after character 9 and before data entry starts again from character 0 Confirm number 3 Repeat the operations described in steps...

Страница 19: ...ome device configurations allow entering the magnitude k M Once the number has been entered as after step 3 keys Up and Down allow enabling the magnitude K kilo or not Press OK to confirm the magnitud...

Страница 20: ...st use PWD A password can be set by the user to protect the Configuration menu and avoid any unwanted modification to the device settings At the first use it is mandatory to define a password The pass...

Страница 21: ...se two wire and 1 CT 6 3 CT ratio Ct P Ct S D1M is capable to measure current only via indirect connection by means of current transformers CTs 5A or 1A It is needed to set the transformation ratio of...

Страница 22: ...mary Vt P and secondary Vt S CFG ISTL VT 1 When the number of the primary VT is set press Button OK 2 Use Button Up and Button Down to select the magnitude 3 Press button OK to confirm the setting of...

Страница 23: ...nstallation Settings related to the installation conditions I O Input Output Settings related to DO ALM Alarm Definition of alarm conditions COM Communication Settings related to the embedded communic...

Страница 24: ...et factory settings Reset Energy Clear register of all energy Reset NOTF Clear the logs of warning error and alarm Reset Global Complete reset of the device RESET FACTORY Reset Factory settings restor...

Страница 25: ...ll notification will be cleared after the reset notification including alarms warnings and errors CFG UNT RST NTF RESET Global Complete reset of the device except for the settings and the audit log in...

Страница 26: ...on FW Firmware version CRC A method for Error Detection and Correction SN Serial Number D1M D1M Device Type Energy Saving ENS In this menu it is possible to define the inactivity time in order to limi...

Страница 27: ...ounted contain the activities as below User could read the times through HMI and communication Description 1 CT Primary setting 2 CT Secondary setting 3 VT Primary setting 4 VT Secondary setting 5 Wir...

Страница 28: ...G UNT HOMEPAGE Auto Scroll pages Auto Scroll pages can be set for an auto scroll time loop scrolling as below two modes a All Real Time measurement pages b Phase measurements to three phase system mea...

Страница 29: ...al Apparent Import Energy ISEN and Total Apparent Export Energy ESEN The pulse width can be configured between 10ms and 990ms and it can be set via the HMI and communication The pulse width should sat...

Страница 30: ...ransformers for voltage measurement if any Wiring TYPE Set the type of network and number of wires on which the device is installed The three items above must be set during the first startup For detai...

Страница 31: ...10 100 1000 5000 pulses for each kWh kvarh kVAh or 10 50 100 pulses for each Wh varh VAh Manual setting 1 and 999999 pulses for each each MWh Mvarh MVAh The pulse width could be configured once DOs w...

Страница 32: ...and the delay the alarm will be generated and when the alarm variable recovers to the normal range and exceeds the hysteresis and delay the alarm will be released Alarm can be connected to certain DO...

Страница 33: ...n OK to go to the event and modify the configurations If certain event needs to be deleted from the alarm list the alarm variable is selected as NONE For details see VARIABLE VARIABLE Select one varia...

Страница 34: ...merical value and magnitude Different variables correspond to different thresholds magnitudes and units and you need to select variables before setting SETPOINT Variable Value range Active Power 0 999...

Страница 35: ...LM HYS DELAY DELAY is used to verify whether the variable value really exceeds the limit or is recovered and its setting range is 1 900s CFG ALM TIM LOG All alarms are by default in UNLOG mode meaning...

Страница 36: ...m event can be connected with certain DO and different alarms can be connected to the same DO CFG ALM POT The optional Dos include DO1 DO2 and NONE Only the DOs configured as alarm output can appear i...

Страница 37: ...embedded communication protocols Based on product version following configuration menu is available Communication Protocol Parameter Description Modbus RTU ADD Bus address BAU Baud rate PAR Byte forma...

Страница 38: ...COM PAR The optional byte formats include BYTE Description 8E1 8 even parity bits and 1 stop bit 8O1 8 odd parity bits and 1 stop bit 8N1 8 No Parity bits and 1 stop bit Address ADD For the devices t...

Страница 39: ...ll the parameters measured by D1M Specifically it includes the following menus Menu Description REAL Real time measurements ENRG Energy measurements PWQT Power quality I O State of digital input outpu...

Страница 40: ...ses VLL average of 3 phases I and active power total VLN Phase voltage VLL Line voltage I Current P Per phase active power when WIRI is selected as 1N1T this data is absent PT Total active power Q Per...

Страница 41: ...rted active energy PEN EXP Total exported active energy QEN IMP Total imported reactive energy QEN EXP Total exported reactive energy SEN IMP Total imported apparent energy SEN EXP Total exported appa...

Страница 42: ...42 D1M 15 MULTIMETER USER MANUAL 8 3 Power Quality PWQT RED PWQT PWQT Description PF Per phase power factor when WIRI is selected as 3 3T 3 2T 3 1T or 1N1T this data is absent PFT Total power factor...

Страница 43: ...of status and or pulses for DO according to the product version Menu Description DO STA State of digital output port DO1 PUL DO1 Pulse counter DO2 PUL DO2 Pulse counter RED I 0 The state classificati...

Страница 44: ...tions and device settings ERR Errors list related to the device and to its self diagnostics Alarms ALM ALM is generated based on the Alarm configured by the user When the conditions meet the alarm par...

Страница 45: ...Missing I1 MISS Current 1 Missing I2 MISS Current 2 Missing I3 MISS Current 3 Missing I1 REVES Current 1 Reverse I2 REVES Current 2 Reverse I3 REVES Current 3 Reverse I12 REVES Current 1 with 2 Rever...

Страница 46: ...d and it will not disappear until the error is solved ERROR comprises error count and specific error message RED NTF ERR Error Definition LOG ERR Audit log error FLSH ERR Flash chip error or RAM memor...

Страница 47: ...8 6 Power Outage PWF PWF is used to record the number and time of power outage The maximum record number is 999 RED NTF PWF In additional record the power off as a warning in warning list light up the...

Страница 48: ...ER USER MANUAL 9 Conclusion Thank you for using ABB D1M 15 series Multimeter and reviewing this user manual In the future if you encounter any problems please contact ABB technical support we will be...

Страница 49: ......

Страница 50: ...ABB LV Installation Materials Co Ltd Beijing Electrification Business Area No 17 Kangding Street Beijing Economic Technological Development Area 100176 www abb com low voltage 400 820 9696...

Отзывы: