Page 18
© Copyright 2021 ABB. All rights reserved.
Step
Action
6
Connect Four
-
48V
DC
branch circuits to the DC source
Notes:
1.
Each feed supplies half of the shelf. A&B feeds for side 1 and A&B feeds for side 2.
2.
Size each circuit to support 35 Amp List 2 Drains –
18
-
6AWG 2.
3.
Verify minimum loop cable length per
Table 9.
4.
-
48V Returns (RTN) connections must be grounded.
1. Pull connector straight off of its header.
2. Strip wire 1/2 inch
3. Insert wire fully into wire entry
4. Torque screw to 16 in
-
lb (1.7Nm)
5. Repeat from 2 for all wires
6. Push connector straight onto its header
Figure 9 Converter Shelf Input Power Connections
7
Close the distribution door.
Repeat from Step 2 for each Converter Shelves.
-
48V A
(1
-
6)
-
48V B
(1
-
6)
RTN
(1
-
6)
RTN
(7
-
12)
-
48V A
(7
-
12)
-
48V B
(7
-
12)
A
-
48V (1
-
6) Input
B
-
48V (1
-
6) Input
RTN (1
-
6)
RTN (7
-
12)
A
-
48V (7
-
12) Input
B
-
48V (7
-
12) Input
Screw
2
Reference NEC Table 310
-
16 for applications of not more than three conductors in a raceway and correction factors for Ambient Temperatures over 30°C. Each
installation will vary and the installer should review NEC cabling requirements as well as local practice to ensure proper cable sizing is achieved for the local
conditions.
Содержание CPS2400U
Страница 2: ...Page 2 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 8: ...Page 8 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 12: ...Page 12 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 30: ...Page 30 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Страница 49: ...Page 49 Copyright 2021 ABB All rights reserved Figure 33 Converter Slot Fillers ...