Operation
ABB, 1SBC159107M020
1
19
6.6 Downloading an Application
Connect the RS232 port on the PC to the COM1 port on the CP415 using a
TK401 cable. The connection can also be made according to the illustration be-
low:
Set the dip switch
SW7 = ON
. After the self-test, the system menu will be
displayed on the screen and the operator terminal is ready to download the
application.
Start CP400Soft and open the application file to be downloaded. Make sure that
the communication parameters are correctly configured. Also remember to
compile the file before downloading it. The file has to be compiled every time a
change has been made in the file before downloading it.
Then select
Application/Download Firmware/Application
in CP400Soft if it is
a first time to download the application to the operator terminal; otherwise, se-
lect
Application/Download Application
. The following appears on the screen
while the operator terminal is downloading:
CP415
COM1
9-pin male
PC
RS232
9-pin female
CP415
COM1
9-pin male
IPC485 or RS485
interface
converter
RXD 2
2 RD
RS485+ 1
D+
TXD 3
3 SD
RS485- 6
D-
GND 5
5 SG
RTS 7
1 CD
CTS 8
4 DTR
6 DSR
7 RTS
8 CTS
Warning:
To avoid an electrical shock, be sure to switch off the power before connecting the