3.4
Ramp/Soak Profile Control
Level r – Profile Control
Program Time Units
Select the time units required
hrS
–
Hours
MINS
–
Minutes
The time base selected applies to all segments.
Select Ramp Type
Select the ramp type required
tIME
–
Ramp time
rAtE
–
Ramp rate
The ramp type selected applies to all segments.
Next Program Select Source
See Rear Fold-out/Table C –
Digital Sources
Only programs which have been set up in the profile program level,
level t, can be selected.
Program Run/Hold Source
The run/hold source is level triggered i.e. the active logic state must be
maintained to select the alternative function.
See Rear Fold-out/Table C –
Digital Sources
Note. If a program is run using
Program Run/Hold Source
,
'Operator Hold' is disabled until the
Program Run/Hold Source
has been
de-activated. The
Program Hold Source
and front panel switches have no
effect.
Program Run Source
The run source is leading edge triggered i.e. the active logic state can be
removed after the function is selected.
See Rear Fold-out/Table C,
Digital Sources
Continued…
•1
A digital input becomes active when a volt-free contact is closed or a low TTL signal is applied.