![ABB COMMANDER 300 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/abb/commander-300/commander-300_operating-instructions-manual_3529504022.webp)
20
…8
COMMUNICATION
8.6.3
Heat/Cool Parameters
Parameter
Mnemonic
Command
Reply Interpretation
Read
(R)
Write
(W)
Control Page Parameters (Heat/Cool)
Cycle Time (Cool)
CC
Yes
Yes
1.0 to 300.0
Proportional Band (Cool)
L2
Yes
Yes
0.1 to 999.9
Integral Action Time (Cool)
L3
Yes
Yes
1 to 7200 (7201 = OFF)
Manual Reset (Cool)
L4
Yes
Yes
0.0 to 99.9
Crossover Output Value
Q1
Yes
Yes
0.0. to 100.0
Transition Bandwidth
Q2
Yes
Yes
0.0 to 100.0
Output Off Hysteresis
Q3
Yes
Yes
0.0 to 25.0
Heat Output High Limit
Q4
Yes
Yes
0.0. to 100.0
Cool Output High/Low Limit
Y1
Yes
Yes
0.0. to 100.0
Heat Output
Y2
Yes
No
0.0 to 100.0
Cool Output
Y3
Yes
No
0.0 to 100.0