COMMUNICATION…
8.6.1 General Parameters…
Parameter
Mnemonic
Command
Reply Interpretation
Read
(R)
Write
(W)
Remote Set Point Set Up Parameters
Remote Set Point
Input Type
I2
Yes
Yes
0 = mV
1 = mA
2 = Volts
3 = Ohms
4 = Thermocouple
5 = RTD
Remote Set Point
Lineariser Type
W2
Yes
Yes
As for Lineariser Type in Set-up Process
Variable Input Parameters
Remote Set Point
Lineariser Units
U2
Yes
Yes
0 = Degrees C
1 = Degrees F
Remote Set Point
Lineariser Full Scale
X2
Yes
Yes
–420 to +3100
Remote Set Point
Lineariser Range Zero
E2
Yes
Yes
–420 to +3100
Remote Set Point
Range Full Scale
S2
Yes
Yes
–1999 to +1999
Remote Set Point
Decimal Pt. Position
P2
Yes
Yes
0 to 2
Remote Set Point
Range Zero
Z2
Yes
Yes
–1999 to +1999
Remote Set Point Fault
Detect Level
2L
Yes
Yes
0 to 100.0
Remote Set Point
Default Action
2A
Yes
Yes
0 = None
1 = Local
2 = Default Set point
Remote Set Point
Default Set Point
2S
Yes
Yes
Any value within the programmed display
range
Set-Up Position Feedback Parameters
Position Feedback
Input Type
I3
Yes
Yes
0 = mV
1 = mA
2 = Volts
3 = Ohms
Position Feedback
Range Full Scale
S3
Yes
Yes
–1999 to +1999
Position Feedback
Decimal Pt. Position
P3
Yes
Yes
0 to 2 positions
Position Feedback
Range Zero
Z3
Yes
Yes
–1999 to +1999
Position Feedback
Fault Detect Level
3L
Yes
Yes
0 to 100.0
Position Feedback
Default Action
3A
Yes
Yes
0 = None
1 = Hold