5
…3.1
Set Up Input
Page Header – Set Up Input (Process Variable)
To advance to
Set Up Pen Range Page
press the
switch.
Select Channel
Select the channel to be programmed:
PV–4
–
process variable on channel 4
PV–3
–
process variable on channel 3
PFb–2
–
valve position feedback on controller 2
only displayed if selected in the
rSP–2
–
remote set point on controller 2
Input Asignment Page
PV–2
–
process variable on channel 2
PFb–1
–
valve position feedback on controller 1
only displayed if selected in the
rSP–1
–
remote set point on controller 1
Input Asignment Page
PV–1
–
process variable on channel 1
NONE
–
None
✶
Note. In the remaining frames press the
switch to view the channel selected.
Input Type (Process Variable)
Caution. Ensure the correct input link positions are selected and the input is wired
correctly – see Section 6,
CONNECTIONS & LINKS
.
Select the input type required:
rtd
–
Resistance thermometer
tCPL
–
Thermocouple
VOLt
–
Voltage
LO OHM
–
Low resistance (
≤
750
Ω
)
HI OHM
–
High resistance (>750
Ω
)
MAMP
–
Current
MU.Lt
–
Millivolt (
≤
150mV)
NONE
–
None
Linearizer Type
Select the linearizer type required:
5/2
–
x
5/2
3/2
–
x
3/2
SQrt
–
Square Root
rtd
–
Resistance thermometer
tC–b
–
Type B thermocouple
tC–N
–
Type N thermocouple
tC–E
–
Type E thermocouple
tC–J
–
Type J thermocouple
tC–t
–
Type T thermocouple
tC–S
–
Type S thermocouple
tC–r
–
Type R thermocouple
tC–K
–
Type K thermocouple
NONE
–
No linearizer
Continued on next page.
SEt UP
INPUt
SELECt
PV–4
PV–3
PFb–2
rSP–2
PV–2
PFb–1
rSP–1
PV–1
NONE
INtYP
rtd
tCPL
VOLt
LO OHM
HI OHM
MAMP
MVLt
NONE
NONE
LNtYP
5/2
3/2
SQrt
rtd
tC–b
tC–N
tC–E
tC–J
tC–t
tC–S
tC–r
tC–K
NONE
Not available on position feedback input
Open channel flow applications
3
BASIC CONFIGURATION LEVEL…