![ABB COMMANDER 1900 Series Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/abb/commander-1900-series/commander-1900-series_programming-manual_267038.webp)
36
4.3
Set Up Control
Information.
• Control types – Current Proportioning, Time Proportioning (and On/Off), Position-proportioning (motorized valve control
with feedback), Boundless and Heat/Cool.
• Programmable power-up control modes and outputs.
• Reverse and direct control actions.
• High and low output limits.
• Programmable fault actions – enable fault actions on any of the inputs (process variable, remote set point and position
feedback) to be controlled.
P.I.D.
Control
Terms
On/Off
Control
Process
Variable
Set Point
Time Proportioning
Analog Output
Relay or
Digital
Outpuu
4 to 20mA
Relay or
Digital
Outpuu
C1900 Controller
Feedback
Process
SEt UP
ContrL
PFMOdE
SELECt
CtrL 2
CtrL 1
NONE
C-tYPE
bNdLSS
P-PrOP
Ht-CL
Std
------
Page Header – Set Up Control.
Select Controller
Select the controller to be programmed (1 or 2).
✶
Note. In the remaining frames press the
switch to view the controller selected.
Control Type
Select the control type required:
bNdLSS
–
(Boundless) for motorized valve control, without position feedback
P-PrOP
–
(Position-Proportioning) motorized valve control, with position feedback
Ht-C
L
–
(Heat/Cool) dual output control
Std
–
(Standard) current proportioning, time proportioning and on/off
Continued on page 38.
4.3.1
Set Up Control Page (control type)
Fig. 4.5 Standard Control Schematic Diagram
…4
CONTROL CONFIGURATION LEVEL