13
Station Automation
COM600
Product version: 3.4
1MRS756764 B
Electrostatic discharge test
• Contact discharge
• Air discharge
According to IEC 61000-4-2,
IEC 60255-22-2
6 kV
8 kV
Radio frequency field immunity
According to IEC 61000-4-3
and IEC 60255-22-3
10 V/m (80% amp.mod.)
f=80...1000 MHz
10 V/m (pulse mod.) f=900
MHz
Fast transient
• Power supply
• RJ-45 port
According to IEC 61000-4-4
and IEC 60255-22-4
2 kV
1 kV
Surge immunity
• Power supply
According to IEC 61000-4-5
and IEC 60255-22-5
2 kV line-to-earth,
1 kV line-to-line
Conducted radio frequency disturbance
According to IEC 61000-4-6
and IEC 60255-22-6
10 V (80% ampl. mod.)
f= 150 kHz...80 MHz
Power frequency (50 Hz) magnetic field
According to IEC 61000-4-8,
300 A/m, continuous
Voltage dips and short interruptions
According to IEC 61000-4-11
30% reduction for 10 ms
60% reduction for 100 ms
60% reduction for 1000 ms
>95% reduction for 5000 ms
Emission tests
According to EN 55011,
and IEC60255-25, class A
Table 10. Environmental conditions
Description
Value
Operating temperature range
-25...+70ºC
1) 2)
Relative humidity range, non-condensing
5...95% at +40ºC
Storage temperature
-40...+70ºC
1) Without any option cards
2) With Ethernet option card: 0…+55°C, with Serial option card: 0…+55°C, with LON option card: 0…+70°C