Document no. 1SVC 510 810 M0000 A1
12 / 16
Program setup
The suitable program must be set on the CM-UFD.M21 in accordance with the application. If the
CM-UFD.M21 is sealed/locked (red LED
lightning), sealing has to be deactivated first.
Pr Connection
Threshold
values
Voltage
*1 3 AC with N
230 V
2
3 AC w/o N
Low voltage
1x overvoltage, 1x undervoltage
1x overfrequency, 1x underfrequency
10 min average value, 1x vector shift
400 V
3
3 AC with N
57.7 V
4
3 AC w/o N
100 V
5
3 AC with N
230V
6
3 AC w/o N
Medium voltage
2x overvoltage, 2x undervoltage
2x overfrequency, 2x underfrequency
10 min average value, 1x vector shift
400V
* default setting
Adjustment process:
If present, remove seal (only authorised person)
Apply control supply voltage at A1-A2
Slightly lift the button cover and turn 180°
Actuate the small blue button by strong pressing on the button cover (LED starts flashing)
until the green LED
is lightning.
Press
button 1x
Display
8
Info.
8
Press
button 5x
Display
8
Pr 1.
8
Set the program with the buttons
Press
button 1x
Display
8
no.
8
Press
button 1x
Display
8
yes.
8
Press
button
Device resets and starts with the newly selected program
Hint: When changing programs, all parameters of the selected program are reset to “default settings“
(
see table „Default settings“
). Only change the parameters after having selected the correct
program.
Technical data
Rated control supply voltage U
s
:
24-240 V AC/DC, DC / 40-70 Hz, <5 VA
Tolerance
-15…+10
%
Output relays:
2 c/o contacts
Max. switching voltage
400 V AC
Conventional thermal current I
th
6
A
Inrush current (at 10 % ED)
25 A max. 4 s / 50 A max. 1 s
Rated operational current I
e
(AC15)
230 V AC / 1.5 A
Fuse rating to achieve short-ciruit protection max. gG/gL 6 A
Mechanical lifetime
30 x 10
6
switching cycles
Electrical lifetime
1 x 10
6
switching cycles at AC12, 230 V, 6 A
Output voltage - transistor outputs Q1-Q5
Operational voltage V
Q
4.5-27 V DC
Max. current consumption Q1…Q5
20 mA / output
Input circuit - feedback contacts
Y0 – Y1/2
No-load voltage at the control inputs
15-35 V DC
Feedback time section switch 0.5-99.0
s
selectable
Subject to change without prior notice