Type CKO Overcurrent Relay
41-101.3A
5
ENERGY REQUIREMENTS
TYPE CKO-2 TIME OVERCURRENT UNITS
VOLT AMPERES
††
CONTINUOUS
ONE SECOND
POWER
AT
AT 3 TIMES
AT 10 TIMES
AT 20 TIMES
AMPERE
RATING
RATING
†
FACTOR
TAP VALUE
TAP VALUE
TAP VALUE
TAP VALUE
RANGE
TAP
(AMPERES)
(AMPERES)
ANGLE
ø
CURRENT
CURRENT
CURRENT
CURRENT
0.5
0.91
28
58
4.8
39.6
256
790
0.6
0.96
28
57
4.9
39.8
270
851
0.8
1.18
28
53
5.0
42.7
308
1024
0.5-2.5
1.0
1.37
28
50
5.3
45.4
348
1220
1.5
1.95
28
40
6.2
54.4
435
1740
2.0
2.24
28
36
7.2
65.4
580
2280
2.5
2.50
28
29
7.9
73.6
700
2850
2.0
3.1
110
59
5.04
38.7
262
800
2.5
4.0
110
55
5.13
39.8
280
920
3.0
4.4
110
51
5.37
*40.8
312
1008
2-6
3.5
4.8
110
47
5.53
42.8
329
1120
4.0
5.2
110
45
5.72
46.0
360
1216
5.0
5.6
110
41
5.90
50.3
420
1500
6.0
6.0
110
37
6.54
54.9
474
1800
4.0
7.3
230
65
4.92
39.1
268
848
5.0
8.0
230
50
5.20
42.0
305
1020
6.0
8.8
230
47
5.34
44.1
330
1128
4-12
7.0
9.6
230
46
5.53
45.8
364
1260
8.0
10.4
230
43
5.86
49.9
400
1408
10.0
11.2
230
37
6.60
55.5
470
1720
12.0
12.0
230
34
7.00
62.3
528
2064
†
Thermal capacities for short times other than one second maybe calculated on the basis of time being inversely proportional
to the square of the current.
ø
Degrees current lags voltage at tap value current.
††
Voltages taken with Rectox type voltmeter.