ABB CDPI-01 Скачать руководство пользователя страница 19

CDPI-01 communication adapter module   19

Example: Chaining a PC through a commercial converter

This figure shows how to chain a PC to several drives through a 

commercial converter.

USB - 
RS485 or 
Ethernet - 
RS485 
converter

Drive 1

CDPI-01

X101

X102

S100 = ON

1)

S101 =

 

ON or 

Drive 2

CDPI-01

X101 X102

S100 = OFF

S101 = OFF

2)

Drive n (max. 32)

CDPI-01

X101 X102

S100 = ON

S101 = OFF

2)

Data A

Data B

1) 

Must be switched on in the first module on the bus if the converter 

does not have a termination switch.

2)

 Must be switched on at some point on the bus if the converter does not 

have an internal biasing resistor.

3) 

For the X101 pin allocation, see section 

Pin allocation of connectors 

X101 and X102

 on page 

22

.

            OFF

2)

3)

Содержание CDPI-01

Страница 1: ...Options for ABB drives User s manual CDPI 01 communication adapter module Power and productivity Jll ft ft for a better world fii DD ...

Страница 2: ...the inside of the back cover For manuals not available in the Document library contact your local ABB representative Drive manuals and guides Code EN Multilingual ACS580 01 manuals 9AKK105713A8085 Option manuals and guides CDPI 01 communication adapter module user s manual 3AXD50000009929 ACS AP x Assistant control panels user s manual 3AUA0000085685 ...

Страница 3: ...g the panel cabling to the drive 10 Alternative 1 Routing the cabling inside the drive 10 Alternative 2 Routing the cabling outside the drive 13 Bus termination and chaining examples 17 Example Chaining a control panel 17 Example Chaining a PC through a control panel 18 Example Chaining a PC through a commercial converter 19 Start up 20 Before you start 20 Setting the parameters Example for ACS580...

Страница 4: ...4 Table of contents Further information Product and service inquiries 23 Product training 23 Providing feedback on ABB Drives manuals 23 Document library on the Internet 23 ...

Страница 5: ...ded for people who plan the installation install start up use and service the CDPI 01 communication adapter module Before you do work on the module read this manual and the applicable drive manual that contains the hardware and safety instructions for the product in question You are expected to know the fundamentals of electricity wiring electrical components and electrical schematic symbols The m...

Страница 6: ... to connect a remote ACS AP x control panel to the drive or to chain the control panel or a PC to several drives on a panel bus The panel bus can have a maximum of 32 nodes The control panel PC is the master while the drives equipped with the communication adapter module are followers Layout 1 2 3 4 5 6 7 7 8 ...

Страница 7: ...100 to the drive control unit 3 Termination switch S100 4 Bias switch S101 5 Connector X101 for connecting a control panel or a PC 6 Connector X102 for chaining a panel bus 7 Cable hole locations Used when the cabling connected to the module is routed outside the drive 8 Clip for attaching the module to the drive ...

Страница 8: ...crewdriver and a set of suitable bits If you install the communication adapter module inside the drive you need a T20 torx screwdriver for removing the cover and a cutter knife for cutting a hole to the rubber grommet at the cable lead through Selecting the cables Use straight connected CAT5e UTP FTP cables with RJ 45 connectors General cabling instructions Arrange the cables as far away from the ...

Страница 9: ...ion adapter module is installed in the same slot as the control panel If a control panel is attached to the drive remove the control panel first as follows Note If the drive is in local control and you do not stop the drive before you remove the control panel the motor will stop and the drive will trip to a fault 1 If the drive is running stop the drive 2 Release the control panel by pressing the ...

Страница 10: ...ver 3 Use a multimeter to make sure that there are no parts under voltage in reach 4 Cut an adequate hole into the rubber grommet Slide the grommet onto the cable Slide the cable through the hole of the bottom plate and attach the grommet to the hole 5 Route the cable first under the cable clamp a and then anticlockwise round the panel housing b 6 Connect the panel cable to module connector X101 F...

Страница 11: ...er modules The control panel terminates the bus at its end so only the other end of the bus must be terminated Bias switch S101 Must be OFF in all modules 9 Attach the module to the drive Place the bottom end of the module into the bottom of the slot in the drive Pivot the module and push the upper part until you hear a click 10 Adjust the cable s and tighten the clamp a 11 Put the drive cover bac...

Страница 12: ...12 CDPI 01 communication adapter module 5a 5b ...

Страница 13: ...ches at the back of the module Termination switch S100 If the module is connected to one drive only set the switch to OFF If you have several drives on the panel bus set the switch to ON in the last module of the bus OFF in all other modules The control panel terminates the bus at its end so only the other end of the bus must be terminated Bias switch S101 Must be OFF in all modules 5 Attach the m...

Страница 14: ...14 CDPI 01 communication adapter module 2 ...

Страница 15: ...CDPI 01 communication adapter module 15 3 4 ...

Страница 16: ...16 CDPI 01 communication adapter module 5a 5b 5c ...

Страница 17: ...cable ends Example Chaining a control panel This figure shows how to chain a control panel to several drives Drive 1 CDPI 01 X101 X102 S100 OFF S101 OFF Drive 2 CDPI 01 X101 X102 S100 OFF S101 OFF Drive n max 32 CDPI 01 X101 X102 S100 ON S101 OFF 1 The control panel terminates the bus at its end so only the other end of the bus must be terminated 1 ...

Страница 18: ...rol panel Note When a control panel is used for a panel to PC connection it cannot be used for operating the drive Drive 1 CDPI 01 X101 X102 S100 OFF S101 OFF Drive 2 CDPI 01 X101 X102 S100 OFF S101 OFF Drive n max 32 CDPI 01 X101 X102 S100 ON S101 OFF 1 1 The control panel terminates the bus at its end so only the other end of the bus must be terminated ...

Страница 19: ...S100 ON1 S101 ON or Drive 2 CDPI 01 X101 X102 S100 OFF S101 OFF2 Drive n max 32 CDPI 01 X101 X102 S100 ON S101 OFF2 Data A Data B 1 Must be switched on in the first module on the bus if the converter does not have a termination switch 2 Must be switched on at some point on the bus if the converter does not have an internal biasing resistor 3 For the X101 pin allocation see section Pin allocation o...

Страница 20: ...devices connected to the bus must have a unique node ID It is advisable to reserve ID 1 for spare replacement drives because they have ID 1 as the default factory setting Start numbering from ID 2 3 Set the baud rate of the drive 49 03 Baud rate The baud rate has to be the same for all nodes on the bus 4 Select a suitable value for parameter 49 05 Communication loss action value This parameter def...

Страница 21: ... the drive control unit Degree of protection IP21 when installed Ambient conditions See the drive technical data Package Cardboard Switches Termination switch S100 Bias switch S101 Connectors Unshielded female connector to the drive control unit X100 RJ 45 Shielded female connector for connecting a control panel or a PC X101 RJ 45 Shielded female connector for chaining a panel bus X102 RJ 45 Power...

Страница 22: ...Hi Z Data B 3 TRANS Not connected 4 FAULT Not connected 5 GND Ground 6 GND Ground 7 GND Ground 8 VCC From drive Power supply 15 24 V DC Bus type RS 485 Purpose Used as a panel bus Maximum length 100 m Maximum number of nodes 32 nodes control panel PC and drives Maximum transfer rate 1 Mbit s Medium CAT5e UTP FTP Ethernet cable straight connection Connector RJ 45 ...

Страница 23: ...ormation on ABB product training navigate to www abb com drives and select Training courses Providing feedback on ABB Drives manuals Your comments on our manuals are welcome Go to www abb com drives and select Document Library Manuals feedback form LV AC drives Document library on the Internet You can find manuals and other product documents in PDF format on the Internet Go to www abb com drives a...

Страница 24: ...Contact us www abb com drives www abb com drivespartners 3AXD50000009929 Rev A EN EFFECTIVE 2013 09 30 ...

Отзывы: