8. Adjust the switches at the back of the module.
Termination switch (S100):
•
If the module is connected to one drive only, set the switch
to OFF.
•
If you have several drives on the panel bus, set the switch
to ON in the last module of the bus, OFF in all other
modules. The control panel terminates the bus at its end,
so only the other end of the bus must be terminated.
Bias switch (S101): Must be OFF in all modules.
9. Attach the module to the drive.
•
Place the bottom end of the module into the bottom of the
slot in the drive.
•
Pivot the module and push the upper part until you hear a
click.
10. Adjust the cable(s) and tighten the clamp (a).
11. Put the drive cover back.
For a panel bus chaining example, see section
on page