![ABB CC1600-SC55 Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/abb/cc1600-sc55/cc1600-sc55_quick-start-manual_3045355009.webp)
Page 9
© 2023 ABB. All rights reserved.
CC1600SC55_QSG
Rev 4.0
Step 7 –
Wire the DC Output Option #1
Two DC Output, One AC Input, Alarms
This rectifier configuration will accept up to 2 pairs of 8 AWG Wire in the terminal block located on the left side of
the wiring space. Select a wire and jacket suitable for the application. The DC strain relief hole is a
3/4”
trade size
hole. If the supplied strain relief does not work with the wire selected, use a strain relief that does.
1.
Run the DC output cable through the strain relief fitting, left hole on the strain relief cover .
2.
Strip the outer jacket to reveal 2 inches of inner conductor.
3.
If there are more than 2 conductors in the jacket, apply 1 inch of heat shrink tubing to the conductor that will
be unused, leaving 1/2 inch of free tubing past the end of the conductor to assure that that conductor will
never be energized.
4.
Strip the inner jacket off the two conductors to expose 7/16 inches (11mm) of bare conductor.
5.
Connect the first pair of the wires to the first set of + and
-
48V terminals, toward the left end of the terminal
block. One wire c. The other carries
-
48V. See Information Table on sheet 9
6.
Torque each screw compression fitting to 12 in
-
lbs. using a flat bladed screw driver.3e, or #2 pozi drive
screwdriver.
7.
Pull wire to verify.
8.
Repeat 1
-
7 for the second output using the second strain relief and strain relief hole if desired.
View Shown with DC Output Panel Option #1