background image

41-337.31 C

5

4.4.

Setting Calculations

No calculations are required to set the CA-16.

4.5.

Setting The Relay

No settings are required on the CA-16 relay.

5.0

INSTALLATION

The relays should be mounted on switchboard panels
or their equivalent in a location free from dirt, moisture,
excessive vibration and heat. Mount the relay verti-
cally by means of the four mounting holes on the
flange for the semi-flush type FT case. The mounting
screws may be utilized for grounding the relay. Exter-
nal toothed washers are provided for use in the loca-
tions shown on the outline and drilling plan to facilitate
making a good electrical connection between the relay
case, its mounting screws and the relay panel. Ground
Wires are affixed to the mounting screws as required
for poorly grounded or insulating panels. Other electri-
cal connections may be made directly to the terminals
by means of screws for steel panel mounting.

For detail information on the FT case refer to IL 41-
076 for semi-flush mounting.

6.0

ADJUSTMENTS AND MAINTENANCE

The proper adjustments to insure correct operation of
this relay have been made at the factory. Upon
receipt of the relay, no customer adjustments should
be required.

6.1.

Acceptance Check

The following check is recommended to insure that
the relay is in proper working order. The relay should
be connected per Figure 8.

A.

Minimum Trip Current

Apply current to terminals 12 and 13 of the relay. The
relay should operate as follows:

CA-16

0.15 amperes 

±

5%

B.

Percentage Differential Characteristic

Apply 16 amperes to terminals 9 and 19 of the CA-16
relay. The contacts should close when the following
operating current is applied to the relay with connec-
tions of Figure 8.

CA-16

17.0 amperes 

±

7%

Check each individual restraint winding by applying
50 amperes to each winding. Apply sufficient operat-

ing current to the operating circuit until the contacts
just close. The operating current should be:

CA-16

3.9 to 5.1 amperes

C.

Time Curve

Apply 20 amperes to terminals 12 and 13 of the
relays. The contacts should close in the following
times:

CA-16

58 to 68 Milliseconds

D.

Indicating Contactor Switch (ICS)

Close the main relay contacts and pass sufficient dc
current through the trip circuit to close the contacts of
the ICS. This value of current should not be greater
than the particular ICS nameplate rating. The indica-
tor target should drop freely.

Repeat above except pass 85% of ICS nameplate
rating current. Contacts should not pickup and target
should not drop.

E.

Sensitive Fault Detector

Apply current to terminals 14 and 15 of the relay. The
fault detector should operate between the limits of
0.142 to 0.158 amperes.

6.2.

Routine Maintenance

All contacts should be periodically cleaned. A contact
burnisher is recommended for this purpose.
(S#182A836H01). The use of abrasive material for
cleaning contacts is not recommended, because of
the danger of embedding small particles in the face
of the soft silver and thus impairing the contact.

7.0

CALIBRATION

Use the following procedure for calibrating the relay if
the relay has been taken apart for repairs or the
adjustments disturbed. This procedure should not be
used until it is apparent that the relay is not in proper
working order. (See “Acceptance Check”.)

7.1.

Contacts

Adjust the adjustable stop screw on the upper disc of
the relay so that a contact separation of 0.050 inch is
obtained between the moving contact and the sta-
tionary contact. Lock the screw with the nut provided
for the purpose.

7.2.

Minimum Trip

The relay should be level for this test. Minimum trip

Содержание CA-16

Страница 1: ......

Страница 2: ...41 337 31 C 2 Figure 1 CA 16 Front View Figure 2 CA 16 Rear View ...

Страница 3: ...ed from causing contact bouncing A micarta disc is fastened to the bottom of the guide rod by two small nuts Its position determines the pick up current of the ele ment The auto transformer is designed to saturate at high values of current to limit the amount of current to the contactor switch 2 3 1 Indicating Contactor Switch Unit ICS The dc indicating contactor switch is a small clapper type dev...

Страница 4: ...g the lead located in front of the tap block to the desired setting by means of a screw connection 4 2 Trip Circuit Constants Indicating Contactor Switch ICS 0 2 amp rating 8 5 ohms dc 1 0 amp rating 0 37 ohms dc 2 0 amp rating 0 10 ohms dc ENERGY REQUIREMENTS Burden of each restraint coil at 5 amperes VOLT AMPERES POWER FACTOR 75 7 Continuous Rating 14 amperes 1 second rating 460 amperes Burden o...

Страница 5: ...onnec tions of Figure 8 CA 16 17 0 amperes 7 Check each individual restraint winding by applying 50 amperes to each winding Apply sufficient operat ing current to the operating circuit until the contacts just close The operating current should be CA 16 3 9 to 5 1 amperes C Time Curve Apply 20 amperes to terminals 12 and 13 of the relays The contacts should close in the following times CA 16 58 to ...

Страница 6: ... may be removed and the tab holding the target reformed slightly if necessary However care should be exercised so that the target will not drop with a slight jar If the pickup is low the front cover must be removed and the leaf springs on each side bent outward equally 7 6 Sensitive Fault Detector Loosen the lock nut at the top of the element and run the core screw down until it is flush with the ...

Страница 7: ...41 337 31 C 7 Figure 3 Internal Schematic of the Type CA 16 Bus Relay Sub 1 3532A95 ...

Страница 8: ...41 337 31 C 8 Figure 4 Typical Time Curves of the CA 16 Differential Relay Sub 1 537956 ...

Страница 9: ...41 337 31 C 9 Figure 5 Typical Burden Characteristics of the Types CA 16 and CA 26 Relays Curve 537957 ...

Страница 10: ...41 337 31 C 10 Figure 6 External Schematic of One Set of Type CA 16 Relays for the Protection of a Three and Four Circuit Bus Sub 5 187A424 ...

Страница 11: ...41 337 31 C 11 Figure 7 External Schematic of the Type CA 16 Relays for Protection of Six Circuit Bus with Three Feeder Groups Sub 5 187A425 ...

Страница 12: ...41 337 31 C 12 Figure 8 Diagram of Test Connections for the CA 16 Relay Sub 4 187A426 ...

Страница 13: ...41 337 31 C 13 Figure 9 Percentage Slope Curve of the CA 16 Relay with One Restraint Winding Sub 1 849A450 ...

Страница 14: ...41 337 31 C 14 Figure 10 Percentage Slope Curve of the CA 16 Relay with Six Restraint Windings in Series Sub 2 849A343 ...

Страница 15: ......

Страница 16: ...ABB Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 Telephone 1 954 752 6700 Fax 1 954 345 5329 www abb com substation automation IL 41 337 31 Revision C ABB ...

Отзывы: