background image

41-337.31 C

4

4.0

CHARACTERISTICS

4.1.

CA-16 Bus Relay

This relay has variable percentage characteristics
which means that the operating coil current
required to close the relay contacts, expressed in
percent of the total restraint current, varies with the
magnitude of the restraint current. The relay sensi-
tivity is high, corresponding to a low percentage
ratio, at light currents, and its sensitivity is low, cor-
responding to high percentage unbalance, at high
currents. The relay is made sensitive at low cur-
rents in order to detect light internal faults on the
bus being protected. At the same time, however, its
reduced sensitivity at the higher currents allows the
various current transformers involved to depart
from their true ratio to a large extent without caus-
ing false tripping of the relay for external faults.

The variable percentage characteristics are particu-
larly advantageous when severe saturation of cur-
rent transformers is caused by the dc component of
asymmetrical short circuits. In the case of buses
located close to generating stations where the dc
components decay slowly, the breakdown in ratio of
the current transformers will be much greater than
would ever be expected from a consideration of the
usual ratio curves of the current transformers
involved.

The time of operation of the relay is shown in Fig-
ure 4.

The main contacts will safely close 30 amperes at
250 volts dc and the seal-in contacts of the indicat-
ing contactor switch will safely carry this current
long enough to trip a circuit breaker.

The indicating contactor switch has two taps that
provide a pick-up setting of 0.2 or 2 amperes. To
change taps requires connecting the lead located in
front of the tap block to the desired setting by
means of a screw connection.

4.2.

Trip Circuit Constants

Indicating Contactor Switch (ICS)

0.2 amp rating

8.5 ohms dc

1.0 amp rating

0.37 ohms dc

2.0 amp rating

0.10 ohms dc

ENERGY REQUIREMENTS

Burden of each restraint coil at 5 amperes

VOLT AMPERES

POWER FACTOR

.75

.7

Continuous Rating

14 amperes

1 second rating

460 amperes

Burden of operating Circuit

VOLT AMPERES

VARIABLE (See

 

Figure 5)

Continuous rating 8 amperes

1 second rating 280 amperes

4.3.

Connections

4.3.1. CA-16

To determine the ac connections, identify each pri-
mary circuit as either a “source” or “feeder”. As
defined here, a feeder contributes only a small por-
tion of the total fault-current contribution for a bus
fault. Otherwise, the circuit is a source. Next lump a
number of feeders into a “feeder group” by paralleling
feeder ct’s, taking the precaution that each feeder
group has less than 14 amperes load current
(restraint coil continuous rating). Also each feeder
group should not contribute more than 10% of the
total phase or ground-fault current for a bus fault if
Figure 7 is to be used.

Connect per Figure 6 with three or four bus “circuit.”
The term “circuit” refers to a source or to a feeder
group. For example, assume a bus consisting of 2
sources and 6 feeders. Further, assume that the
feeders are lumped into 2 feeder groups. The bus
now reduces to four circuits

If the bus reduces to more than four circuits, parallel
source-circuit ct’s or source-and feeder circuit ct’s
until only four circuits remain. Then connect these
four sets of ct’s to the relays per Figure 6. The excep-
tion to this rule occurs when the application consists
of three feeder groups. Then Figure 7 applies.

With 3 feeder groups and more than 3 sources, par-
allel source ct’s until the application reduces to 6 cir-
cuits; then, connect to the relays per Figure 7.

Содержание CA-16

Страница 1: ......

Страница 2: ...41 337 31 C 2 Figure 1 CA 16 Front View Figure 2 CA 16 Rear View ...

Страница 3: ...ed from causing contact bouncing A micarta disc is fastened to the bottom of the guide rod by two small nuts Its position determines the pick up current of the ele ment The auto transformer is designed to saturate at high values of current to limit the amount of current to the contactor switch 2 3 1 Indicating Contactor Switch Unit ICS The dc indicating contactor switch is a small clapper type dev...

Страница 4: ...g the lead located in front of the tap block to the desired setting by means of a screw connection 4 2 Trip Circuit Constants Indicating Contactor Switch ICS 0 2 amp rating 8 5 ohms dc 1 0 amp rating 0 37 ohms dc 2 0 amp rating 0 10 ohms dc ENERGY REQUIREMENTS Burden of each restraint coil at 5 amperes VOLT AMPERES POWER FACTOR 75 7 Continuous Rating 14 amperes 1 second rating 460 amperes Burden o...

Страница 5: ...onnec tions of Figure 8 CA 16 17 0 amperes 7 Check each individual restraint winding by applying 50 amperes to each winding Apply sufficient operat ing current to the operating circuit until the contacts just close The operating current should be CA 16 3 9 to 5 1 amperes C Time Curve Apply 20 amperes to terminals 12 and 13 of the relays The contacts should close in the following times CA 16 58 to ...

Страница 6: ... may be removed and the tab holding the target reformed slightly if necessary However care should be exercised so that the target will not drop with a slight jar If the pickup is low the front cover must be removed and the leaf springs on each side bent outward equally 7 6 Sensitive Fault Detector Loosen the lock nut at the top of the element and run the core screw down until it is flush with the ...

Страница 7: ...41 337 31 C 7 Figure 3 Internal Schematic of the Type CA 16 Bus Relay Sub 1 3532A95 ...

Страница 8: ...41 337 31 C 8 Figure 4 Typical Time Curves of the CA 16 Differential Relay Sub 1 537956 ...

Страница 9: ...41 337 31 C 9 Figure 5 Typical Burden Characteristics of the Types CA 16 and CA 26 Relays Curve 537957 ...

Страница 10: ...41 337 31 C 10 Figure 6 External Schematic of One Set of Type CA 16 Relays for the Protection of a Three and Four Circuit Bus Sub 5 187A424 ...

Страница 11: ...41 337 31 C 11 Figure 7 External Schematic of the Type CA 16 Relays for Protection of Six Circuit Bus with Three Feeder Groups Sub 5 187A425 ...

Страница 12: ...41 337 31 C 12 Figure 8 Diagram of Test Connections for the CA 16 Relay Sub 4 187A426 ...

Страница 13: ...41 337 31 C 13 Figure 9 Percentage Slope Curve of the CA 16 Relay with One Restraint Winding Sub 1 849A450 ...

Страница 14: ...41 337 31 C 14 Figure 10 Percentage Slope Curve of the CA 16 Relay with Six Restraint Windings in Series Sub 2 849A343 ...

Страница 15: ......

Страница 16: ...ABB Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 Telephone 1 954 752 6700 Fax 1 954 345 5329 www abb com substation automation IL 41 337 31 Revision C ABB ...

Отзывы: