Feedforward Bias
[–100.0% to 100.0%]
Control Deadband
When the process variable is in the deadband, changes to the control
output due to proportional and integral action are suppressed. When a
cascade template is selected, the control deadband is applied to the
master output only.
[In engineering units or 'OFF']
Heat/Cool Output 1 Start
This parameter defines the PID output value above which Output 1 (heat)
becomes active.
[0.0 to 100.0%]
Heat/Cool Output 2 Start
This parameter defines the PID output value below which Output 2 (cool)
becomes active.
[0.0 to
≤
Y1st %] – see Heat/Cool Output 1
Return to top of page
…3
SET UP MODE
2.20...2.23
…3.2
Level 2 – Tune
50.0
Y2.St
2...23
50.0
Y1.St
2...22
OFF
Cbnd
2..21
Deadband
Set Point
LEV2
tUNE
0.0
FFbS
2.20
•1
Process Variable
Control Output
•2
•2
•1
Only displayed if a feedforward template is selected – see Section 4.2, Basic Configuration/ Template Application.
Not applied to Control Output when Feedforward Gain (frame 2.19) is set to 'OFF'.
•2
Only displayed if a Heat/Cool output type is selected – see Section 4.2, Basic Configuration/ Output Type.
Output 2
PID Output
0%
100%
100%
0%
Y2.St
Y1.St
Output 1
Output 2
PID Output
0%
100%
100%
0%
Y2.St
Y1.St
Output 1
Reverse-direct
or direct-reverse
Reverse-reverse
or direct-direct