AT  CU R R E NT  I N STRU M E NT  TR A N S FOR M E R 

I N S T R U C T I O N S  FO R  I N S TA L L AT I O N ,  USE  A N D  M A I N T EN A N C E


02 AT35/41 mouting 
points

03  AT38 mounting 
points

2. 

 Ground always the metallic base of the 
instrument transformer.

3. 

 Connect always one terminal of each sec-
ondary winding of the transformer to the 
earth. When the secondary of trans-
former is interconnected, there should 
be only one grounded point to prevent 
accidental paralleling with system 
grounding wire.

4. 

 Always short-circuit the secondary of the 
current transformer, which is not cur-
rently in use, to prevent secondary volt-
ages, which may be hazardous to per-
sonnel or damaging to the transformer’s 
secondary. The secondary like this must 
be additionally grounded.

Mounting
Mounting points are showed on picture below

The AT transformer is mounted in different 
ways-using rings to fix the transformer directly to 
the bushing, using flanges, or other ways of fixa-
tion. The mounting is not a part of transformer 
delivery and the customer is fully responsible for 
installation in the right way.

Tightening torques

AT35 (M12)

30 Nm

AT38 (M16)

30 Nm

AT41 (M16)

50 Nm

The producer has not any liability for incorrect 
mounted form or possible consequences of it. 
Nuts and threaded rots are delivered on cus-
tomer request.

Connection of transformer primary side
The AT transformers don´t have its own primary 
conductor. The primary conductor is designed as 
a bushing with its own insulation, or insulated ca-
ble.

Connection of the transformer secondary side
Secondary outlets are marked by color. Which 
color is assigned to which wire you can see in ta-
ble below.

Outlets marking

test wire (measure side)

black marked with M

test wire (earth side)

black mark with Ground

screen earth

black mark with Ground

secondary wire xS1 
(X1, Y1, Z1, U1, V1, W1)

black and marked with core/
terminal no.

secondary wire xS2 
(X2, Y2, Z2, U2, V2, W2)

red and marked with core/
terminal no.

secondary wire xS3 
(X3, Y3, Z3, U3, V3, W3)

yellow and marked with core/
terminal no.

secondary wire xS4 
(X4, Y4, Z4, U4, V4, W4)

blue and marked with core/
terminal no.

secondary wire xS5 
(X5, Y5, Z5, U5, V5, W5)

grey and marked with core/
terminal no.

secondary wire xS6 
(X6, Y6, Z6, U6, V6, W6)

brown and marked with core/
terminal no.

4. Instructions for use

Current instrument transformers are used:

•  to convert large currents in the primary circuit 

to an appropriate level for secondary circuit 
equipment (relays and meters);

•  to insulate primary and secondary circuit from 

each other to protect the secondary equipment 
from the harmful effects of large current ap-
pearing during the operation (short circuits).

 


02


03

Mounting points

Lifting points

Mounting points

Содержание AT35

Страница 1: ... PRODUCTS FOR HIGH VOLTAGE APPLICATION AT Current Instrument Transformer Instruction for Installation use and maintenance ...

Страница 2: ...ructions 4 Mounting 4 Connection of transformer primary side 4 Connection of transformer secondary side 4 4 Instructions for use 5 Routine test report 5 5 Maintenance instructions before installation 5 6 Transport Storage 5 7 Disposal 5 8 Handling 5 9 Normative references 6 10 Dimensions 5 11 Lifetime 5 12 Service 7 Appendix 1 Examples of outlets 8 Appendix 2 Dimensional drawings AT35 and AT41 Dim...

Страница 3: ...ended current 9 rated output burden 10 accuracy classes 11 year of manufacture 12 serial number Label abbreviation definitions 3 Instruction for installation General information Instrument transformer is an electrical equip ment and the electrical installation of the instru ment transformer can be done by skilled person nel only The level of experience age and eligibility criteria for persons work...

Страница 4: ...hreaded rots are delivered on cus tomer request Connection of transformer primary side The AT transformers don t have its own primary conductor The primary conductor is designed as a bushing with its own insulation or insulated ca ble Connection of the transformer secondary side Secondary outlets are marked by color Which color is assigned to which wire you can see in ta ble below Outlets marking ...

Страница 5: ...rage the transformers have to be pro tected from direct impact of solar radiation The transformers are delivered in wooden crates or fixed on transport pallets Transported transformers must be protected to avoid any damages Right option of transport must be wisely chosen 7 Disposal Materials used in instrument transformers are considered as materials without environmental impact and materials are ...

Страница 6: ...ed IEC 60044 1 IEC 60044 6 IEC 61869 2 AS 60044 1 ČSN EN 60044 1 ČSN EN 60044 6 IEEE Std C57 13 6 2005 ANSI C57 13 1978 CSA Std CAN3 C13 M83 BS EN 60044 1 When agreed transformers made in accordance with other standards can also be supplied or in accordance with other release version of the above standards 10 Dimensions Dimensions of the current transformers acc ap pendix 2 11 Lifetime The product...

Страница 7: ...7 Appendix 1 Examples of outlets ...

Страница 8: ...d depends on customer request The fixing parts are a part of a delivery mounting parts can be ordered separately as an attachment Testing primary Secondary outlets SIGN VALUE Variant C NOTE Variant C with optional testing primary see catalogue and optional length of secondary outlets depending on customer request The fixing part are a part of delivery mounting parts can be ordered separately as an...

Страница 9: ...ry secondary outlets screening electrodes is optional and depends on customer request The fixing parts are a part of a delivery mounting parts can be ordered separately as an attachment AT38 Testing primary Secondary outlets Secondary electrodes 1000 1 0 0 0 ...

Страница 10: ...le lack of information in this document We reserve all rights in this document and in the subject matter and illustrations con tained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Copyright 2018 ABB All rights reserved C O N TA C T U S ABB s r o EPDS Brno Videnska 117 619 00 Brno Czech Repu...

Отзывы: