Name

Description

Value range

Use HW

handshaking

(CTS/RTS)

Enables CTS/RTS handshaking if set to “Yes”.

No, Yes

Gateway

mode

 

 

Gateway

mode

If set to “Network master to serial slaves”, the slaves are on the

serial side.

Network master

to serial slaves

Protocols

 

 

Serial protocol

Defines the Modbus protocol that serial devices use in serial

communication. The possible settings are Modbus RTU protocol

and Modbus ASCII protocol. ModbusRTU is recommended

because it is more efficient.

ModbusRTU,

ModbusASCII

Network

protocol

Defines the TCP/IP and Modbus protocol used on network

communication. Possible protocols are Modbus TCP protocol

over TCP, Modbus RTU protocol over TCP, Modbus RTU

protocol over UDP, and Modbus ASCII protocol over UDP.

ModbusTCP,

ModbusRTU

over TCP,

ModbusRTU

over UDP,

ModbusASCII

over TCP,

ModbusASCII

over UDP

Framing

 

 

Slave

response

timeout

Defines the time in microseconds (millionths of a second) how

long the device waits for the response from a Modbus slave. If

the response is not received, the device can generate and return

a Modbus gateway exception. The reply timeout of the Modbus

master must be greater than the gateway device timeout.

Otherwise, the flow of request-reply communication is violated.

The device does not accept a new request before the reply from

the slave is received or the reply timeout is elapsed. The delays

in network communication can vary especially in wireless

networks. When the slaves are located on the network side, ping

or another method should be used to estimate the delay packets

spend on network.

0...90 000 000

(0...90

seconds)

Inter-frame

timeout

Defines the idle time in microseconds (millionths of a second)

that marks the end of Modbus frame in serial communication. If

the value is zero, the device uses the standard 4 character time.

The recommendation is to use a value as small as possible to

speed up communication and increase the value if problems

arise. Some PC programs can insert unexpected delays

between serial characters.

0...2 000 000

(0...2 seconds)

Exceptions

 

 

Generate

gateway

exceptions

Defines if the device generates and returns a Modbus gateway

exception message to the master if no valid reply is not received

from the slave. If set to “Yes”, the generation of exceptions is

enabled. This functionality is useful for debugging.

No, Yes

Pass gateway

exceptions

If set to “Yes”, gateway exception replies from the slave side are

passed to the master. If set to “No”, the replies are filtered away.

No, Yes

Network

server settings

 

 

Table continues on next page

Section 10

1MRS758456 H

Modbus application settings

46

ARG600 Single SIM Variant

User Manual

Содержание ARG600 Single SIM Variant

Страница 1: ... Wireless Gateway ARG600 Single SIM Variant User Manual ...

Страница 2: ......

Страница 3: ...Document ID 1MRS758456 Issued 2022 06 20 Revision H Product version 3 4 Copyright 2022 ABB All rights reserved ...

Страница 4: ...escribed in this document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB is a registered trademark of the ABB Group All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders Warranty Please inquire about the terms of warranty from your nearest ...

Страница 5: ...ce which should be connected to a secure network It is the sole responsibility of the person or entity responsible for network administration to ensure a secure connection to the network and to take the necessary measures such as but not limited to installation of firewalls application of authentication measures encryption of data installation of anti virus programs etc to protect the product and ...

Страница 6: ...n systems air traffic control direct life support machines or weapons systems in which the failure of the hardware or software described in this manual could lead directly to death personal injury or severe physical or environmental damage To prevent damage both the product and any terminal devices must always be switched off before connecting or disconnecting any cables It should be ascertained t...

Страница 7: ...ail mounting 13 Product information label 13 Firmware version 13 Section 3 Physical connections 15 Communication connections 15 Serial ports 15 Console serial port 1 15 Serial port 2 16 Ethernet 18 Wireless network 18 Section 4 Getting started 21 Connecting cables 21 Connection principle 21 Logging in 22 User interface 22 Setting Ethernet port function to LAN 22 Configuring mobile WAN 23 Configuri...

Страница 8: ...tory default settings 32 Updating the firmware 32 Saving configuration profiles 32 Section 8 Service configuration 33 Configuring services 33 Service parameters 33 Section 9 IEC 104 application settings 37 The use of the IEC 104 protocol 37 Configuring IEC 104 application settings 37 IEC 104 application settings 37 Section 10 Modbus application settings 43 Modbus Gateway properties 43 Modbus mode ...

Страница 9: ...roduct documentation set Product series and product specific manuals can be downloaded from the ABB Web site abb com mediumvoltage 1 3 2 Document revision history Document revision date Product version History A 2015 12 18 A First release B 2017 09 22 3 4 Content updated to correspond to the product version C 2019 04 24 3 4 7 Content updated to correspond to the product version D 2020 07 09 3 4 7 ...

Страница 10: ...e of Wireless Gateway devices 1MRS758451 Product series and product specific manuals can be downloaded from the ABB Web site abb com mediumvoltage 1 4 Symbols and conventions 1 4 1 Symbols The electrical warning icon indicates the presence of a hazard which could result in electrical shock The warning icon indicates the presence of a hazard which could result in personal injury The caution icon in...

Страница 11: ...all warning and caution notices 1 4 2 Document conventions A particular convention may not be used in this manual Abbreviations and acronyms are spelled out in the glossary The glossary also contains definitions of important terms Menu paths are presented in bold Select Main menu Settings Parameter names are shown in italics The function can be enabled and disabled with the Operation setting Param...

Страница 12: ...6 ...

Страница 13: ... DNP3 TCP SCADA system In this case the DNP3 protocol is transferred over TCP IP communication transparent serial gateway mode Wireless Gateway ARG600 can be utilized for various industrial and utility applications to maximize the benefits Industrial grade TCP IP router several serial and TCP IP based field devices can be integrated into a central supervisory and control system SCADA Integrated pr...

Страница 14: ...C limited 240 VA power source that fulfills the requirements of standard IEC 60950 1 2 Console serial port 3 Application serial ports 4 LAN WAN port 5 Power switch 6 Console serial port switch 7 DIP switches Power supply connector The device has a VDC power supply connector Section 2 1MRS758456 H ARG600 overview 8 ARG600 Single SIM Variant User Manual ...

Страница 15: ...ole access When it is disabled both serial ports may be used as an application serial port When the switch is in the right position RS1 is in serial port mode and when in the left position RS1 is in console mode DIP switches The DIP switches select an application port RS2 mode and settings RS 232 or RS 485 By default all DIP switches are set to the 0 position RS 232 mode DIP switches 2 4 apply onl...

Страница 16: ...S 422 termination on pins 2 and 8 If biasing and or termination is required for the RS 485 half duplex 2 wire mode enable RS 422 biasing termination with DIP switches and manually connect pins 2 7 and 3 8 together at the application port RS 2 Ethernet connector The device has an RJ 45 connector for 10 100 Mbps Ethernet connection The maximum length of the Ethernet cable is 100 m 2 2 2 Back panel T...

Страница 17: ...e an earthing screw near the antenna connector When available it has to be used for the protective earthing 2 2 3 Side panel The ten LEDs on the side panel of the device indicate the status of the device Only five of them are connected The LEDs are numbered 1 10 starting from the rear panel side 1MRS758456 H Section 2 ARG600 overview ARG600 Single SIM Variant 11 User Manual ...

Страница 18: ...rting Off VPN connection is disabled 3 Power Error On Operating power is turned on Off Operating power is turned off 4 Function On Device is starting Flashing Device is operating normally Off Device is not operational 5 Eth 1 On Ethernet link is up Flashing Ethernet link is transferring data Off Ethernet link down 6 Eth 2 LED reserved for future use 7 Led 1 LED reserved for future use 8 Led 2 LED ...

Страница 19: ...ting holes for optional DIN rail mounting brackets The order code for the DIN rail mounting kit is 2RCA028234 DIN rail clips set consisting of a plastic clip and screws 2 4 Product information label The product label contains basic information about the unit such as product name serial number and Ethernet MAC address 2 5 Firmware version The device s firmware version is visible on the welcome page...

Страница 20: ...14 ...

Страница 21: ...The console switch enables or disables console access When the switch is in the right position serial port 1 is in the serial port mode and when it is in the left position serial port 1 is in the console mode The console switch is located below the serial port 1 connector Turn off power from the device before toggling the console switch as the switch position is read during the boot sequence only ...

Страница 22: ... 1 1 2 Serial port 2 Serial port 2 can be configured to multiple serial formats RS 232 422 485 The default is RS 232 GUID 9F6668AA EBAB 46B5 A1AF 35D8AE3E6C12 V1 EN US Figure 6 Application serial port Table 5 Application serial port pinout RS 232 PIN Function 1 DCD 2 RXD 3 TXD 4 DTR 5 GND 6 DSR 7 RTS 8 CTS 9 RI Section 3 1MRS758456 H Physical connections 16 ARG600 Single SIM Variant User Manual ...

Страница 23: ...G 0 OFF 1 ON Enables RS 422 biasing on pins 2 and 8 4 TERMINATION 0 OFF 1 ON Enables RS 422 termination on pins 2 and 8 If biasing and or termination is required for the RS 485 half duplex 2 wire mode enable RS 422 biasing termination with DIP switches and manually connect pins 2 7 and 3 8 together at the application port RS 2 Do not connect RS 422 or RS 485 cables to a serial port configured to t...

Страница 24: ... 1 3 Wireless network The device supports cellular connectivity 2G 3G LTE allowing the use of wireless applications The practical data transfer rates depend on the subscription details and wireless network capacity The device with wireless interface includes an SMA female type connector for an external antenna Any kind of external 50 Ω wide band antenna can be used intended for GPRS 3G or LTE freq...

Страница 25: ... PIN code query is enabled check that the ARG600 configurator has the correct PIN code entered in the wireless WAN submenu 1MRS758456 H Section 3 Physical connections ARG600 Single SIM Variant 19 User Manual ...

Страница 26: ...20 ...

Страница 27: ...sh 4 1 1 Connection principle The device has configurable network interfaces Ethernet LAN WAN port Mobile WAN cellular interface The device supports cellular connectivity 2G 3G LTE allowing the use of wireless applications The Mobile WAN interface is used for connecting the device to the cellular network The Ethernet LAN is used for connecting other Ethernet devices to the device s local network T...

Страница 28: ...e the password before connecting the product to a public network 5 Click Login The Home Page opens 4 2 1 User interface The user interface consists of views that can be opened from the menu in the left pane 4 3 Setting Ethernet port function to LAN Changing Port function to LAN disables automatic IP address detection If Port function is set to the default value auto the Ethernet LAN port tries to ...

Страница 29: ...te to Yes This setting enables the use of the Ethernet WAN or the Mobile WAN as the default route interface 3 If configuring Ethernet WAN as the default gateway in the left pane under Network click Ethernet Port and set Port function to WAN If configuring Mobile WAN as the default gateway skip this step 4 Set the default route To select Ethernet WAN as the default gateway under Primary WAN set Int...

Страница 30: ...24 ...

Страница 31: ... Set Enable to Yes 3 Select a WAN interface 4 Select a Configuration Mode The Manual Static IP Address mode requires entering the values in the Manual Settings fields 5 Click Submit to save the settings Use the Connectivity Monitor settings when WAN redundancy functionality is required The Connectivity Monitor keeps checking the connection to the given remote host to determine the network status I...

Страница 32: ...the access point s username in the Username field 4 3 Type the access point s password in the Password field 5 If the device acts as a wireless router to Ethernet devices and DNS is needed enter the DNS settings Set DNS Selection to From Network to set up the device to receive DNS server IP addresses automatically from the cellular network Set DNS Selection to Manual to set up the device to use DN...

Страница 33: ...ne Mobile WAN Ethernet WAN Ethernet WAN Secondary These three settings configure the high level default gateways They must be configured to enable default route Backup WAN Interface None Mobile WAN Ethernet WAN Secondary Backup WAN Interface None Mobile WAN Ethernet WAN Ethernet WAN Secondary OpenVPN Client Settings Interface Any WAN Ethernet WAN Wireless WAN Ethernet LAN This setting defines whic...

Страница 34: ...d the device is defined as the DNS server for LAN devices either manually or through DHCP and the device forwards the name queries to the actual DNS server and back to the LAN devices 1 In the left pane under Services click Common 2 Set Use DNS Proxy to Yes 3 Click Submit to save the settings 5 6 Checking network status The device has user interface views and LEDs that show network status and are ...

Страница 35: ...SCII serial device protocol 6 2 Serial gateway The serial gateway feature enables data from the serial port attached device to be routed to Ethernet mobile network serial over IP and vice versa Serial gateway processes the transmitted data transparently and does not alter it any way except for buffering it for transmission Because of the transparent communication any protocols can be used in actua...

Страница 36: ...30 ...

Страница 37: ...me The time zone can be set so that the device shows the time in a local format There is also an NTP server in the device NTP client and server this enables the device to work as NTP server for the LAN devices 3 Click Submit under the Mode setting The lower part of the view is updated if the setting changed 4 Check the time and date settings In the Automatic NTP mode check the settings under Curre...

Страница 38: ... Select the new firmware file 4 Click Update A confirmation dialog opens 5 Click OK to confirm firmware The update takes a few minutes 6 Once the update is finished restart the device 7 5 Saving configuration profiles It is possible to save the device s configuration in a profile for use in other devices or as a backup when updating the firmware The configuration can be exported as an XML file 1 I...

Страница 39: ...S responder The multicast domain name system is a protocol that enables Mac OS X machines on LAN to find the device using its hostname for example arctic 02xxyy No Yes SSH Server The SSH secure shell is an encrypted network protocol for safe remote command line connections It is replacing the Telnet protocol SSH Server Determines if logging into the device using SSH is allowed The device has inter...

Страница 40: ... IP address Usually the last IP address of the subnet Default lease time Given to clients that don t request a specific lease length empty 10800 Maximum lease time The maximum lease time given to clients empty 10800 NTP Servers List of NTP servers comma separated LPR Servers List of line printer LPR servers comma separated WINS Servers List of WINS servers comma separated Table 13 DynDNS client Na...

Страница 41: ...ection Registration password Password needed to register to server with HTTPS protocol This password should not be entered after registration unless re registering is necessary Protocol Patrol communication protocol HTTPS SSH Connection interval Defines how often to report to server Seconds Server Information Server address server port Server IP address and the port the server listens If no value ...

Страница 42: ...ng mode is recommended Polling continuous Options Backup active configuration to server When set to Yes copies encrypted version of the XML configuration file to the server No Yes Allow remote management Enables remote management by Patrol server No Yes Allow LAN device scan Allows periodical local network scan for ABB devices Currently the supported device is RIO600 No Yes Section 8 1MRS758456 H ...

Страница 43: ...nd change settings in the view that opens 3 Click Submit to save the settings 9 3 IEC 104 application settings Table 16 IEC 104 application settings Name Description Value range Basic settings Enable IEC 104 gateway Enables or disables IEC 104 to IEC 101 gateway functionality No Yes Serial settings The serial settings define the properties of physical serial communication between the device and an...

Страница 44: ...n is rejected If the set value is Yes the present connection is terminated and the new connection is accepted It is recommendable to set this value to Yes in normal configurations having only one IEC 104 master No Yes Max clients Max clients defines the maximun number of connections redundancy group 1 3 IEC 104 settings The IEC 104 settings define the properties of IEC 104 link layer and applicati...

Страница 45: ...ndard defines value 2 1 2 3 Info object address length This defines the length of IEC 104 Information object address ASDU header field in bytes 1 2 3 IEC 101 settings The IEC 101 settings define the properties of IEC 101 link layer and application layer parameters as described in the IEC 60870 5 101 standard The IEC 101 communication is carried out between the device and a IEC 101 Slave link addre...

Страница 46: ...nvert an ASDU type Original type to another Applied type type e g in cases when the IEC implementation differs between master and slaves No Yes IEC 101 ASDU type The original ASDU type searched by ASDU type replacer 0 255 IEC 104 ASDU type The new ASDU type is replaced by the original type 0 255 Convert short IEC 101 time stamps Defines if 56 bit timestamps are converted to 24 bit No Yes Packet co...

Страница 47: ...et collector before sending the data to the network 1 255 Other settings Write syslog Write syslog defines if the error messages are stored to system log file or not The system log is available by using Web user interface No Yes 1MRS758456 H Section 9 IEC 104 application settings ARG600 Single SIM Variant 41 User Manual ...

Страница 48: ...42 ...

Страница 49: ...number of core properties Supports Modbus RTU and Modbus ASCII serial protocols Supports Modbus TCP Modbus RTU over TCP Modbus RTU over UDP Modbus ASCII over TCP and Modbus ASCII over UDP network protocols Generates and filters out gateway exceptions Makes automatic connection management Enables multiple server sessions over the network Offers unlimited amount of masters on the network side 1MRS75...

Страница 50: ... port being 502 and transmit Modbus requests The device makes conversions between network and serial protocols If the slave does not reply during defined timeout or if the reply is corrupted the device sends gateway exception message back to the master if the exception generation is enabled Otherwise the reply is returned Multiple masters can connect simultaneously to the Gateway which handles the...

Страница 51: ...le serial port or RS 422 485 is required port 2 is recommended If Port 1 is used the console switch of the device must be in the Application position DIP switches below the DB 9 serial connector specify the RS 232 422 485 settings of Port 2 RS1 RS2 Serial settings Speed Defines the serial port speed for Modbus communication in bps The optimal speed depends on the connected Modbus equipment 300 120...

Страница 52: ...tion is violated The device does not accept a new request before the reply from the slave is received or the reply timeout is elapsed The delays in network communication can vary especially in wireless networks When the slaves are located on the network side ping or another method should be used to estimate the delay packets spend on network 0 90 000 000 0 90 seconds Inter frame timeout Defines th...

Страница 53: ... partially closed connection forming new connections is not accepted by the device the time set in parameter Connection idle timeout is elapsed 0 20 Connection idle timeout If there has not been communication on this route during given amount of seconds the device automatically closes the TCP connection to slave and therefore frees the slave s communication resources This is especially useful when...

Страница 54: ...48 ...

Страница 55: ...eing used Access to web user interface does not work Web user interface uses HTTPS for secure web access and it must be specified on the web browser address field like in this example https 10 10 10 10 Access to the Internet with a laptop connected to the device does not work Test the wireless connection 1 Configure wireless connection and verify if it is connected to the network 2 Connect a lapto...

Страница 56: ...50 ...

Страница 57: ...r Power supply 12 48 VDC limited 240 VA power source that fulfills the requirements of standard IEC 60950 1 or IEC 62368 1 Power consumption 7 W Other Internal clock Real time Approvals CE Environmental conditions Temperature range 30 70 C operating 40 85 C storage Humidity 5 85 RH non condensing Protection class IP30 Table 21 Supported protocols Master protocol Slave protocol IEC 60870 5 104 IEC ...

Страница 58: ...r 8 Stop bits 1 or 2 Parity None Even Odd Flow control None RTS CTS Protection 15 kV ESD and short circuit Console RS 232 19200 bps 8 data bits 1 stop bit no parity 8N1 Serial 2 RS 232 DTE RS 422 RS 485 selectable Male DB 9 connector IEC 60870 5 101 protocol support Full serial and modem signals 300 460 800 bps Data bits 7 or 8 Stop bits 1 or 2 Parity None Even Odd Flow control None RTS CTS Protec...

Страница 59: ...ostatic discharge ESD EN 61000 4 2 2008 12 Radiated radiofrequency electromagnetic field EN 61000 4 3 2006 02 Electrical fast transient EFT EN 61000 4 4 2012 04 Surge EN 61000 4 5 2005 11 Conducted radiofrequency electromagnetic field EN 61000 4 6 2008 10 Power frequency magnetic field EN 61000 4 8 2009 09 Table 24 RoHS and REACH compliancy Description Reference Directive RoHS directive 2002 95 EC...

Страница 60: ...54 ...

Страница 61: ...Data set ready DTE Data Terminal Equipment DTR Data terminal ready Ethernet A standard for connecting a family of frame based computer networking technologies into a LAN GND Ground earth HTTPS Hypertext Transfer Protocol Secure LAN Local area network LED Light emitting diode Modbus A serial communication protocol developed by the Modicon company in 1979 Originally used for communication in PLCs an...

Страница 62: ...exchange data SCADA Supervision control and data acquisition SIM Subscriber identity module SNTP Simple Network Time Protocol TCP Transmission Control Protocol TCP IP Transmission Control Protocol Internet Protocol TXD Transmit exchange data UDP User datagram protocol VPN Virtual Private Network WAN Wide area network Section 13 1MRS758456 H Glossary 56 ARG600 Single SIM Variant User Manual ...

Страница 63: ...57 ...

Страница 64: ...ABB Distribution Solutions P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 abb com mediumvoltage Copyright 2022 ABB All rights reserved 1MRS758456 H ...

Отзывы: