AQUA M A STE R4
| EL EC T R O M AG N E T I C FLO W M E T ER T R A N SM I T T ER | O I/FE T4 0 0 - EN R E V. D
53
Logger Settings*
#
Description
Note
Flow and pressure logging interval
(seconds)
Used to enter an interval time in seconds between logging of flow and pressure values.
Readable level 3
Writable level 4
Flow and pressure retrieved record
interval (seconds)
Used to enter an interval time in seconds between data capture when retrieving flow and pressure
values
Editable
Totalizer Logging Hour
Hour of day totals are recorded
Editable
Clear Logging Data
Erases all logging data
Editable
Earliest Logger Data/Time
Informs start date/time of log
Pulse Output Settings
Description
Note
Pulse Outputs Configuration
Used to enable/disable pulse outputs. Options: Disabled/Enabled
Editable,
default: Disabled
Pulses Per Unit Volume
Used to enter a value (the quantity) of pulses per unit volume. Ensure Enabled is selected at the
Pulse Outputs Configuration parameter before entering a value at this parameter.
Editable
Pulse Width (ms)
Used to enter the pulse duration (in ms)
Editable
Max Available Pulse Frequency (Hz) Maximum frequency for a given pulse width
Read-only
* Use of high pulse output frequencies and long pulse widths will significantly shorten battery life. Ideally F≤ 5 Hz with width ≤ 2 ms.
Alarm Output Settings
Description
Note
Clear All Alarms
Erases all alarm state
Editable
Alarm Output Configuration
Used to enable / disable alarm output. Options: Disabled | Always on | Normally off | Normally on
Editable,
default: Disabled
Totalizer Rollover
0 (Off), 1 (On)
Read-only
Totalizer Reset
0 (Off), 1 (On)
Read-only
Flow Sensor Communications
0 (Off), 1 (On)
Read-only
High Flow Alarm
0 (Off), 1 (On)
Read-only
Low Flow Alarm
0 (Off), 1 (On)
Read-only
Empty Pipe
0 (Off), 1 (On)
Read-only
Pulse output saturated
0 (Off), 1 (On)
Read-only
Battery Power Low Warning
0 (Off), 1 (On)
Read-only
Power Management Settings
Description
Note
System power type
Battery | Mains | Renewable (Factory-set)
Read-only
Current power source
Mains, AC power, Internal battery supply
Read-only
Measurement interval (seconds)
15 s – factory setting
Read-only
Internal supply voltage (V)
Current on-board power supply voltage in voltage
Read-only
Simulation modes
*
Description
Note
Flow Simulation Mode
Used to select the simulation mode. Options: Off | Velocity (mm/s) | Flow (system units)
Editable
Flow Simulation Value
Used to set a value for flow simulation.
Editable
Pulse Output Simulation
Configuration
Used to select the simulation mode for pulse outputs. Options: Off | Forward (DO1) | Reverse (DO2)
Editable
Pulse Output Simulation Frequency
Range 0 to 50 Hz
Editable
Pressure Simulation Mode
Options: Off/On
Editable
Pressure Simulation Value
Used to set a value for pressure simulation
Editable
#
Logger Settings availble with FEX41X/43X only.
* Totalizer changes while a simulation mode is enabled are not saved in non-volatile memory and are reversed when the simulation mode is disabled.