ABB AMVAC Скачать руководство пользователя страница 4

Page 1

1 Important Safety Notes &

Warnings

Equipment operation depends on proper
handling, installation, and maintenance.
Neglecting fundamental requirements may
lead to injury of personnel, failure of the
equipment and property damage.

Safety as described in this instruction book
involves two conditions:

·

  Personal injury.

·

  Product or property damage

.

1.1  Safety Notations

 

Safety  notations  alert  personnel  to

possible death, injury or property damage
situations.  The safety notations appear
before the step in which the condition
applies.  The one safety notice and three
hazard levels notations are:

Personnel installing, operating, or
maintaining this equipment must have
thorough knowledge of all applicable local,
regional, industry, government, and OSHA
safety procedures as well as commonly
accepted safe working practices. Personnel
working in or around this equipment must
also exhibit common sense and good
judgment regarding the potential hazards for
themselves and other personnel in the area.
These instructions are intended for use by
fully qualified personnel and are not a
substitute for adequate training, experience
and supervision.

Should clarification or additional information
be required, refer the matter to your nearest
ABB Sales office.

2 Introduction

2.1  General Instructions

Read these instructions carefully before
installation and use as a guide during
installation and initial operation. Use of
these instructions will facilitate proper
receiving of the equipment and prolong its
useful life.

 WARNING

“Warning” indicates a hazardous
situation that has some probability of
severe injury and substantial property
damage.

 DANGER

“Danger” indicates a hazardous
situation that has a high probability of
death, severe injury, and substantial
property damage.

 CAUTION

“Caution” indicates a hazardous
situation that may result in minor or
moderate injury and/or property
damage.

“NOTICE” indicates a
statement of company policy
as it relates to the safety of
personnel or protection of
property

Courtesy of NationalSwitchgear.com

Содержание AMVAC

Страница 1: ...AMVACTM and ADVACTM Breaker commissioning procedures Courtesy of NationalSwitchgear com...

Страница 2: ...1VAL0501 MB Rev A Oct 2015 Courtesy of NationalSwitchgear com...

Страница 3: ...4 6 Racking DISCONNECT to TEST 10 4 7 In Cell Testing 11 4 8 Racking TEST to CONNECT 11 4 9 Racking CONNECT to TEST 12 4 10 Racking TEST to DISCONNECT 12 4 11 Removal 12 4 12 Standard Color 13 4 13 G...

Страница 4: ...egarding the potential hazards for themselves and other personnel in the area These instructions are intended for use by fully qualified personnel and are not a substitute for adequate training experi...

Страница 5: ...gh center of gravity into account Carry out loading operations only when it has been ensured that all precautionary measures to protect personnel and materials have been taken into consideration 3 3 S...

Страница 6: ...2 Truck mounting WARNING Always follow safe work practices when lifting the circuit breakers to protect the safety of personnel and equipment Always inspect lifting hook for signs of wear or damage be...

Страница 7: ...the lift truck facing toward the truck Figure 4 12 It may be necessary to use the racking handle to rotate the racking screw slightly left or right to free up the truck handles Figure 4 8 Lifting hook...

Страница 8: ...eaker interlock tabs must engage the slots in the lift truck platform before releasing the foot brake and moving the lift truck Lower the lift truck platform before transporting draw out modules from...

Страница 9: ...insure closed indicator is shown c Perform a manual open operation ADVAC only Note if there are any deficiencies during the operations Check the breaker s secondary power requirements listed on the f...

Страница 10: ...tential to the required voltage Figure 4 15 4 Hold for one minute 5 Decrease potential to 0 zero and turn off machine 6 Repeat for the remaining 5 terminals A successful withstand indicates satisfacto...

Страница 11: ...breaker They are a safe distance from the stationary part of the device located on the housings 2 The TEST position disengages the main disconnecting devices and engages the control contacts This posi...

Страница 12: ...ruck foot pedals or lowering the platform with the lift truck control valve Figure 4 19 to lock the locking tabs in the lift truck holding slot The truck platform should be horizontal and aligned with...

Страница 13: ...from the DISCONNECTED position to the TEST Position Press down on the racking release handle on the breaker compartment door Figure 4 22 Figure 4 22 Racking release handle 1 Engage the racking screw o...

Страница 14: ...ther or both the manual opening switch on the gear or associated breaker relay Check that the breaker is open and appropriate indicating lights are active Figure 4 24 Circuit breaker in CONNECTED posi...

Страница 15: ...must disable the UV prior to discharging the breaker 3 Align the locking tabs of the lift truck with the lift truck holding slots in the front of the frame Push the lift truck to the frame to engage...

Страница 16: ...galvanized steel Galvanized steel greatly exceeds the paint qualifications of ANSI C37 20 2 Section 5 2 8 4 14 Primary Disconnect Assemblies Circuit breaker primary disconnects consist primarily of a...

Страница 17: ...ry air vacuum or if necessary with an OSHA approved solvent 4 Check the calibration of protective relays 5 Follow the recommendations of any individual device instructions furnished for maintenance of...

Страница 18: ...or various raw materials The duty of ABB is to facilitate subsequent recycling or disposal at the end of product life During disposal of the product it is always necessary to act in accordance with lo...

Страница 19: ...nclusive or covering all contingencies No warranties expressed or implied including warranties of fitness for a particular purpose or merchantability or warranties of fitness for a particular purpose...

Страница 20: ...f needed Shutter rollers are clean straight and undamaged Truck wheels are parallel with truck sides and rotate freely Wire harness not loose or damaged Components not loose or missing Mechanism is gr...

Страница 21: ...t breaker operates in Connect position Open Close Indicating lights operate as expected Open Close On some ABB Switchgear the Breaker Open indicating light serves as both the breaker is open and that...

Страница 22: ...Page 19 Courtesy of NationalSwitchgear com...

Страница 23: ...is for general information purposes only While ABB strives to keep the information up to date and correct it makes no representations or warranties of any kind express or implied about the completene...

Отзывы: