![ABB ACSM1 Series Скачать руководство пользователя страница 165](http://html.mh-extra.com/html/abb/acsm1-series/acsm1-series_manual_2326165.webp)
Parameters and firmware blocks
165
26.08
ACC COMP DERTIME
(see above)
Defines the derivation time for acceleration (deceleration) compensation. Used to improve the speed
control dynamic reference change.
In order to compensate inertia during acceleration, a derivative of the speed reference is added to the
output of the speed controller. The principle of a derivative action is described for parameter
Note:
The parameter value should be proportional to the total inertia of the load and motor,
ie, approximately 50…100% of the mechanical time constant (
t
mech
). See the mechanical time
constant equation in parameter
If parameter value is set to zero, the function is deactivated.
The figure below shows the speed responses when a high inertia load is accelerated along a ramp.
See also parameter
The source for the acceleration compensation torque can also be selected by parameter
.
0…600 s
Derivation time for acceleration/deceleration compensation.
26.09
ACC COMP FTIME
(see above)
Defines the filter time for the acceleration compensation.
0…1000 ms
Filter time for acceleration compensation. 0 ms = filtering disabled.
26.10
SPEED WIN FUNC
(see above)
Enables or disables speed error window control.
Speed error window control forms a speed supervision function for a speed and torque-controlled
drive (Add operating mode). It supervises the speed error value (speed reference – actual speed). In
the normal operating range, window control keeps the speed controller input at zero. The speed
controller is evoked only if
• the speed error exceeds the upper boundary of the window (parameter
• the absolute value of the negative speed error exceeds the lower boundary of the window
(parameter
).
When the speed error moves outside the window, the exceeding part of the error value is connected to
the speed controller. The speed controller produces a reference term relative to the input and gain of
the speed controller (parameter
) which the torque selector adds to the torque
reference. The result is used as the internal torque reference for the drive.
Example: In a load loss condition, the internal torque reference of the drive is decreased to prevent an
excessive rise of the motor speed. If window control were inactive, the motor speed would rise until a
speed limit of the drive were reached.
(0)
Disabled
Speed error window control inactive.
t
t
%
%
No acceleration compensation
With acceleration compensation
Speed reference
Actual speed
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...