![ABB ACSM1 Series Скачать руководство пользователя страница 89](http://html1.mh-extra.com/html/abb/acsm1-series/acsm1-series_firmware-manual_3347482089.webp)
Parameters and firmware blocks
89
13.12
AI SUPERVISION
FW block: None
Selects how the drive reacts when analogue input signal limit is reached. The limit is selected by
parameter
(0)
NO
No action taken.
(1)
FAULT
The drive trips on fault AI SUPERVISION.
(2)
SPD REF SAFE
The drive generates alarm AI SUPERVISION and sets the speed to
the speed defined by parameter
WARNING!
Make sure that it is safe to continue operation in
case of a communication break.
(3)
LAST SPEED
The drive generates alarm AI SUPERVISION and freezes the speed
to the level the drive was operating at. The speed is determined by the
average speed over the previous 10 seconds.
WARNING!
Make sure that it is safe to continue operation in
case of a communication break.
13.13
AI SUPERVIS ACT
FW block: None
Selects the analogue input signal supervision limit.
Example: If parameter value is set to 0010 (bin), bit 1 AI1>max is selected.
0b0000…0b1111
AI1/AI2 signal supervision selection.
Bit
Supervision selected by parameter
AI SUPERVISION is activated if
0
AI1<min
AI1 signal value falls below the value defined by equation:
par.
- 0.5 mA or V
1
AI1>max
AI1 signal value exceeds the value defined by equation:
par.
+ 0.5 mA or V
2
AI2<min
AI2 signal value falls below the value defined by equation:
par.
- 0.5 mA or V
3
AI2>min
AI2 signal value exceeds the value defined by equation:
par.
+ 0.5 mA or V
Содержание ACSM1 Series
Страница 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Страница 2: ......
Страница 4: ......
Страница 12: ...Table of contents 12...
Страница 49: ...Drive control and features 49...
Страница 282: ...Standard function blocks 282...
Страница 306: ...Application program template 306...
Страница 312: ...Control chain block diagrams 312...
Страница 331: ...331...
Страница 332: ...332...
Страница 333: ......